1 Bed Room - Mental Health, 18m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Code 1BR-MH-18-I
Net Room Area Briefed 18
Hours of Operation 24 Hours
Occupancy 1 patient; 1-2 staff; 1-2 visitors
Description / Special Requirements Single bed room for general mental health patients; natural light and outlook is essential; The room is to be internally lockable with a master keyed lock from the outside; All fittings are to have a breaking strain of not more than 15kg. All glazing (including external windows) is to comply with relevant Standards for Mental Health Facilities. The 1 Bed Room - Mental Health may vary in configuration to suit different Ensuite options including: - 1 BR-MH-A Inboard Ensuite - 1 BR-MH-B Shared Ensuite, access from corridor - 1 BR-MH-C Back-to-Back Ensuites Additional Design Considerations: - Fittings and Furniture: . removable drawers must not to be installed . if hooks are required, they must be collapsible with a breaking strain of not more than 15kg - Door & Joinery Hardware . door hardware and joinery hardware must not provide ligature points -Windows and frames . windows must comply with relevant glazing safety standards . window frames must ensure that glazing will stay in place in the event of an attack; the window must prevent escape after being broken Acoustics: Acoustic privacy is required. Body Protected Electrical Area
Amendment 20.07.2011 First Draft 14.10.2015 Description, FF modified
ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
3092 Wall protection MDF Laminate Bed protection wall panel
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
7001 Windows External windows essential
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 1150mm clear inward & outward opening; lockable; anti-hang door hardware
1088 Skirting Timber Paint 150mmH x 20mm thick nominal securely fixed; or floor vinyl coved skirting
1149 Floor finish Carpet 90/10 Wool/ Nylon Broadloom, 48 oz. vinyl also acceptable
7045 Observation Safety glass Powdercoat Internal window double glazed with integral Venetians, control to corridor side; glazing to be suitable safety glass; internal window optional
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
690 Bed: domestic, single Furniture/ Fitting 3 1
1252 Blind: Venetian integral Furniture/ Fitting 1 3 to external window, observation window (if provided), door glazing
1260 Blind: holland Metalwork 3 1 to external windows, curtains optional; no hanging cords or chains
2150 Chair: patient Furniture/ Fitting 3 1
2655 Chair: visitor Furniture/ Fitting 3 1
4330 Cupboard: wardrobe Furniture/ Fitting 1 1 with fixed shelves; anti-hang door hardware
5910 Desk: built in Furniture/ Fitting 1 1 laminate
12450 Locker: bedside Furniture/ Fitting 3 1 heavy or fixed to wall; drawers must not be removable
13730 Mirror: acrylic Metalwork 1 1 optional; may also use safety glass mirror
17360 Pinboard: fabric covered Furniture/ Fitting 1 1 (velcro compatible) or artwork, optional
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
ID Description Service Category Qty Selection / Remarks
1086 General fluorescent: vandal proof Lighting
1087 Special: reading, vandal proof Lighting 1 may be ceiling recessed
1088 RCD device Power 1 may be located outside room - not on bedhead services panel
5000 Airconditioning HVAC with vandal proof outlet
6065 Special: night lights Lighting vandal proof
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
9000 GPO: Single Power 2
9015 GPO: Cleaner Power 1 locate in corridor outside room
9040 Body protected Power
8080 Emergency call Nurse Call 1 + indicator button & light; may be a duress call system
0 0