ADL Bathroom

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Room Code ADLB-I
Net Room Area Briefed 12
Hours of Operation 24 Hours
Occupancy 1 patient; 1 - 2 staff
Description / Special Requirements A bathroom for patient 'Activities of Daily Living' assessment and training. The ADL Bathroom provides for training of patients to use a domestic bath and toilet, dressing, undressing, grooming and handwashing. Training is also provided for carers including training for safe assisted transfers of a patient from a wheelchair or hoist to the bath, shower or toilet. Facilities include a bath of domestic height and width with an access gap underneath for hoist transfers installed in a corner of the room, a domestic toilet, a handbasin and a separate shower within the room. A low, height adjustable, hand held shower is required over the bath. The room should be as domestic in style as possible. However, durable materials for heavy use and flexibility of fixtures to simulate various home environmnets will be needed to ensure the space can be utilised effectively. Additional Design Requirements: - The shower area must not have a raised hob. - The entrance to the bathroom is to be flush with the adjoining corridor. Additional Design Considerations: - the basin may be height adjustable - the toilet should have adequate circulation to allow access from either side but otherwise be domestic in type Acoustics: Sound attenuation level - Medium. Acoustic privacy required. Body Protected electrical area
Amendment 24.10.2010 - First Draft 26.05.2011 - FE & Services modified 26.10.2015 - Description, Fabric, FF, FE and Services modified
ID Fabric Material Finish Specification Selection Remarks
9110 Doors Solid Core Paint 1 1/2 leaf 1400mm clear opening, privacy latch
2145 Skirting Tiles To match floor Coved or coved floor vinyl skirting also acceptable
1175 Floor finish Tiles Non-slip Ceramic non-slip vinyl also acceptable
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
8040 Door protection Composite Prefinished PVC To door frame
3080 Wall finish Tiles Glazed Full height to wet areas; wall vinyl also acceptable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
6010 Cornice Plasterboard Paint 90mm to match ceiling finish
ID Description Category Group Qty Selection / Remarks
1002 Bench seat: fold up/down Furniture/ Fitting 1 1 in shower area; shower chair also acceptable
2300 Chair: shower Furniture/ Fitting 3 1 provided in lieu of fold up bench seat
3400 Coathook Metalwork 1 2 1 at 1100H
4700 Curtain track: privacy screen Metalwork 1 1 to entry door
4800 Curtain track: shower Metalwork 1 1
5250 Curtain: privacy screen Furniture/ Fitting 3 1 to entry door
5300 Curtain: shower Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 near entry
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6156 Dispenser: soap Furniture/ Fitting 2 1 to basin
6160 Dispenser: toilet paper Furniture/ Fitting 2 1 to toilet grab rails
8430 Grab rail: Bath Metalwork 1 2 combined with hand held shower
8450 Grab rail: Shower Metalwork 1 1 combined with hand held shower
8500 Grab rail: WC, hinged Metalwork 1 1 drop down rail; 1 - with toilet paper dispenser
13700 Mirror Metalwork 1 1 above basin
13800 Mirror: full length Metalwork 1 1 dressing
19100 Waste bin: sanitary Furniture/ Fitting 3 1
20603 Soap/ shampoo holder: recessed Furniture/ Fitting 1 2 1 - to shower; 1 - to bath
23700 Towel rail Metalwork 1 1 with grabrail strength and fixings
23865 Transfer bench Furniture/ Fitting 3 1 not fixed, near bath
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3003 Bidet handset 1 1 ___ ___ ___ ___ yes yes ___ ___ near toilet
3050 Basin: handwash, accessible 1 1 ___ ___ yes ___ yes yes yes ___ single mixer lever tap
3500 Bath: raised 1 1 ___ ___ yes ___ yes yes yes ___ for hoist access
47400 Shower: hand-held 1 2 ___ ___ yes ___ yes yes yes ___ 1 - to shower; 1 - to bath
55600 Toilet suite: standard 1 1 ___ ___ yes ___ ___ yes yes ___
ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 2
5019 Exhaust HVAC
6000 General fluorescent Lighting
8000 Patient/ Staff call Nurse Call 3 + indicator button & light; 1 - to bath; 1 - to shower; 1 - to toilet (with patient call pendant)
8010 Staff/ Nurse assist call Nurse Call 2 + indicator button & light; 1 - near door; 1 - between bath and shower
8080 Emergency call Nurse Call 1 + indicator button & light; 1 - near door
9001 GPO: Double Power 1 locate near door outside room
9040 Body protected Power
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply with relevant electric safety guidelines
5015 Ventilation HVAC
8070 Patient call pendant Nurse Call 1 1 - to toilet
Other Documents
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. $2.99
0 0