Airlock, 6m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Room Code AIRL-6-I
Net Room Area Briefed 6
Hours of Operation 24 Hours
Occupancy N/A
Description / Special Requirements The Airlock is a compartment with controlled pressure and parallel sets of doors, to permit movement between areas at different pressures. The Airlock will provide access to a Unit to maintain air pressurisation. The space should allow access for two persons to pass and for users in wheelchairs. Handrails should be provided for ambulant use. If the Airlock is used for bed/ trolley access the recommended length should be increased to 4100mm with a minimum clear width of 2150mm. Note - if automatic doors are used the length may be reduced due to no door swings. Entry doors may be automatic. Access to the Unit may require intercom or special security provisions.
Amendment 24.10.2010 First Draft 21.10.2015 Description, FE & Services modified 04.07.2016 Document amended to match RLS. 29.08.2016 Services updated
ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
6025 Cornice Aluminium Powdercoat shadow line
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
9125 Doors Solid Core/ Glass Paint 1 1/2 leaf, observation panel 1400mm clear opening, may be automatic, lockable; entry doors may require security features
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
4010 Wall protection Composite Prefinished PVC Combined rail & crash bar at 900mm AFFL for ambulant use; crash rail for trolley only access
ID Description Category Group Qty Selection / Remarks
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
4090 Camera: CCTV security 1 1 yes yes __ __ __ __ __ __ as required
ID Description Service Category Qty Selection / Remarks
1035 Door buzzer Communications 1 optional; to entry door
1040 Intercom Communications 1 optional; to entry door
5000 Airconditioning HVAC may be pressurised
6000 General fluorescent Lighting
9015 GPO: Cleaner Power 1
2120 Camera: CCTV Communications 1 as required
9050 Direct connection Power 1 CCTV camera as required