Airlock - Entry, 6m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Room Code AIRLE-6-I
Net Room Area Briefed 6
Hours of Operation 24 Hours
Occupancy N/A
Description / Special Requirements Airlock associated with a Main Entry Area for wind/ weather protection and to maintain air pressurisation. It will be used by a wide range of people including fully ambulant, persons using a wide range of walking aids, persons in wheelchairs or on trolleys and the general public. The floor finish should be able to catch dirt from footwear or wheelchairs/ trolleys and should be easily cleaned. Sufficient lighting is to be provided. The size of the air lock should allow for several people to enter before the second door opens and should reflect the level of service provision. Entry doors may be glazed and automatic. Walls may also be glazed. 'After-hours' access may require intercom or special security provisions.
Amendment 24.10.2010 First Draft. 16.10.2015 Room Description, Fabric, FFE and Services modified. 28.08.2016 Room description, Fabrics & Services updated
ID Fabric Material Finish Specification Selection Remarks
6025 Cornice Aluminium Powdercoat shadow line
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
1150 Floor finish Composite Slip resistant Floor mat, recessed optional; attention to detailing of recessed mat to avoid trip hazard; full floor mat recommended if provided
2975 Doors Alum framed, safety glass & glazed Powder Coat Sliding door 1800mm clear opening, may be automatic, lockable
5007 Ceiling Plasterboard Paint Bulkhead to conceal automatic door mechanisms
3000 Wall finish Paint Acrylic, washable
7003 Windows Aluminium Framed Powder Coated Clear Glazed full height; safety glass
ID Description Category Group Qty Selection / Remarks
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
7300 Camera: CCTV security 1 1 yes ___ ___ ___ ___ ___ ___ ___ optional
ID Description Service Category Qty Selection / Remarks
1035 Door buzzer Communications 1 optional
1100 TV: CCTV Communications 1 optional
5000 Airconditioning HVAC
9015 GPO: Cleaner Power 1
10020 Card access Security 1 optional; swipe card access
1438 Emergency door release Security 1
2275 Video intercom Communications 1 optional
1983 General fluorescent: downlights Lighting
9050 Direct connection Power 5 optional 1 - for video intercom, 1 - for CCTV camera, 1 - card access, 2 - for automatic doors