Change Cubicle - Accessible

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Room Code CHPT-D-I
Net Room Area Briefed 4
Hours of Operation 24 Hours
Occupancy 1 patient
Description / Special Requirements A screened area for patients using wheelchairs to change, independently or assisted, from street clothes into a hospital gown prior to examination or treatment. Following examination or treatment, the patient will use this type of space to change back into their street clothes. The Change Cubicle should provide facilities for hanging clothes and a bench for the patient to sit on whilst changing. A 1500x1500mm clear circulation space is to be provided in the layout to allow the user to manoeuvre a wheelchair comfortably. Design Considerations: - Provisions for hanging patients' clothing and securing valuables, if these are not to be kept with the patient, should be considered either within this room (if lockable) or in shared secure storage or dedicated patient lockers - Waiting areas for gowned patients should be provided adjacent to the change cubicles with adequate privacy screening - Gowned patients should have access to toilet facilities without passing through public areas Acoustics: Sound attenuation level - medium; acoustic privacy required.
Amendment 24.10.2010 - First Draft 05.05.2011 - Description, Fabric & FF modified 02.09.2015 - Description, Fabric & FF modified
ID Fabric Material Finish Specification Selection Remarks
6025 Cornice Aluminium Powdercoat shadow line
9001 Doors Solid Core Paint Single leaf 920mm clear outward opening, privacy latch. Curtain privacy screen on track may be provided instead
5060 Ceiling Acoustic Prefinished Drop-in tiles, 600x1200
3000 Wall finish Paint Acrylic, washable
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
8040 Door protection Composite Prefinished PVC To door frame
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL as required
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
ID Description Category Group Qty Selection / Remarks
1000 Bench seat Furniture/ Fitting 1 1 A sturdy chair may be provided instead
3400 Coathook Metalwork 1 2 1 at 1200 AFFL
8510 Grab Rail: SS Metalwork 1 1
13700 Mirror Metalwork 1 1 full height, dressing
19800 Shelf: laminate Furniture/ Fitting 1 1 optional; for patient belongings; provide if chair provided
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6000 General fluorescent Lighting
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light, may be located outside cubicle entry
Other Documents