Corridor- Clinical Areas

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Code CORR-CL-I
Net Room Area Briefed 0
Hours of Operation 24 hours
Occupancy N/A
Description / Special Requirements Internal circulation Corridor in a clinical area including Birthing Unit, Neonatal Units (Special Care, General Care, NICU), General Medical Imaging, Ultrasound, Cardiac Investigations (for outpatients such as Stress Testing, ECG) Corridor widths must be sized to allow for the safe movement and passing of trolleys, beds and equipment; 2450mm clear width is recommended. Area (m2) is included in HPU circulation which may be esitmated as a percentage added to the Net Briefed Area or measured off a plan. 1 x GPO-Cleaner should be provided per 10 metres or as per local authority requirements. Corridor lighting, where patients are transported on trolleys, should be positioned to prevent unnecessary glare to patient eyes. Light fittings shall be recessed, flush fitting and sealed to prevent dust ingress.
Amendment 28.08.2017 - First Draft.
ID Fabric Material Finish Specification Selection Remarks
2530 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL, minimum
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
8040 Door protection Composite Prefinished PVC To door frame optional; to be decided at project level.
3000 Wall finish Paint Acrylic, washable
3528 Wall protection Handrail at 900mm AFFL to Corridors accessed by ambulant patients, both sides of Corridor
9225 Doors Solid Core/ Glass Paint Double leaf, observation panel to Corridor zones; 1800mm clear opening; doors widths to ensure ease of movment of trolleys/beds; hold open devices may be applied, magnetic hold open devices to fire doors must be connected to the fire alarm system; entry doors should be lockable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended to perimeter
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL where required; align heights of corner guards with other corridor elements
4020 Wall protection Composite Prefinished PVC Crash rail at 900mm AFFL
5060 Ceiling Acoustic Prefinished Drop-in tiles, 600x1200 mm to centre
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
5830 Dispenser: antiseptic hand rub Furniture/ Fitting 2 1 Number to suit corridor layout and Infection Control policies.
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
8040 Annunciator Nurse Call 1 Ceiling mounted; number to suit corridor layout
9015 GPO: Cleaner Power 1 1 every 10 metres recommended; number and location to comply with local authority requirements
10020 Card access Security 1 To unit entry doors where required
2485 General LED: fully recessed Lighting
0 0