Ensuite - Mental Health

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Code ENS-MH-I
Net Room Area Briefed 5
Hours of Operation 24 Hours
Occupancy 1 patient; 1 staff assisting as required
Description / Special Requirements The Ensuite - Mental Health will provide a shower, toilet and handbasin for use by mental health patients. The Ensuite will be lockable and Master Keyed from the outside with a privacy latch on the inside. The Ensuite - Mental Health may vary in configuration to suit different room types including: - ENS-MH-A Inboard Ensuite with direct access, for 1 or 2 Bed Rooms - ENS-MH-B Inboard Ensuite with access from corridor, for 1 or 2 Bed Rooms - ENS-MH-D Inboard Ensuite for 2 Bed Room, with direct access Acoustics: Sound attenuation level high; Acoustic privacy required Body Protected electrical area Additional Design Considerations: - Two floor wastes will be required - Fittings are to have a breaking strain of not more than 15 kg - Grab rails, shower and door furniture must not provide points for ligature - Cisterns should be concealed - All glazing in the room including mirror to be unbreakable - An 'observation bay' which may include thermostatic mixing & shut off valves and RCD is optional
Amendment 24.10.10, - First Draft
ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
5021 Ceiling Plasterboard Paint, washable Water resistant, flush set, suspended
6010 Cornice Plasterboard Paint 90mm to match ceiling finish
8040 Door protection Composite Prefinished PVC To door frame
9001 Doors Solid Core Paint Single leaf 920 clear outward opening, privacy latch, key lockable as required by safety risk assessment
1175 Floor finish Tiles Non-slip Ceramic vinyl also acceptable
2145 Skirting Tiles To match floor Coved or coved floor vinyl skirting
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
3080 Wall finish Tiles Glazed Full height to wet areas; vinyl also acceptable
ID Description Category Group Qty Selection / Remarks
3400 Coathook Metalwork 1 2 collapsible
4800 Curtain track: shower Metalwork 1 1 plastic, ceiling mounted/ recessed
5300 Curtain: shower Furniture/ Fitting 3 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 no sharp cutting edges
6156 Dispenser: soap Furniture/ Fitting 2 1 optional
6160 Dispenser: toilet paper Furniture/ Fitting 1 1
8400 Grab rail: WC Metalwork 1 1 vertical with infill, ligature resistant
8450 Grab rail: Shower Metalwork 1 1 vertical with infill, ligature resistant
13730 Mirror: acrylic Metalwork 1 1
19910 Shelf: vanity Furniture/ Fitting 1 1 recessed
20650 Soap/ shampoo holder Furniture/ Fitting 1 1 recessed
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to hand basin
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2850 Basin: handwash, Type C 1 1 ___ ___ yes ___ yes yes yes ___
3003 Bidet handset 1 1 ___ ___ ___ ___ yes yes ___ ___
47550 Shower: corrective services 1 1 ___ ___ yes ___ yes yes yes ___
55605 Toilet suite: patient 1 1 ___ ___ yes ___ ___ yes yes ___ concealed cistern
ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 2
5000 Airconditioning HVAC
5019 Exhaust HVAC for heat/ steam
8000 Patient/ Staff call Nurse Call 2 + indicator button & light
0 0