Ensuite - Super VIP

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. $2.99
Room Code ENS-SVIP-I
Net Room Area Briefed 20
Hours of Operation 24 Hours
Occupancy 1 patient; 1 staff assisting
Description / Special Requirements An Ensuite - Super VIP is for a patient to wash, shave, groom themselves, shower and use the toilet, either independently or with assistance. The area and layout must accommodate an assisting nurse, patient lifter and assisted wheelchair access. The Ensuite - Super VIP may include a bath. An island bath will require an increase in the room area. Acoustics: Sound attenuation level - High. Acoustic privacy required. Body Protected Electrical Area Additional Design Requirements: - The shower floor must not have a raised hob - The entrance is to be flush with the adjoining flooring - The door is to be fitted with escape hardware
Amendment 24.10.10, - First Draft 26.05.11, - Fabric, FF & Services modified 08.04.13, - Fabric modified;
ID Fabric Material Finish Specification Selection Remarks
5021 Ceiling Plasterboard Paint, washable Water resistant, flush set, suspended
1250 Floor finish Tiles Polished Stone/ Marble 15mm
2147 Skirting Tiles To match floor
1324 Wall finish Tiles Polished Stone/ Marble, full height
9001 Doors Solid Core Paint Single leaf 920 clear outward opening, privacy latch, emergency release
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
150 Air flowmeter Furniture/ Fitting 3 1 optional
350 Artwork Furniture/ Fitting 3 2 optional
530 Basin vanity top Furniture/ Fitting 1 1 stone/ granite
1000 Bench seat Furniture/ Fitting 1 3 stone; 2 to bath area; 1 in shower
1465 Bracket: suction bottle Furniture/ Fitting 2 1 optional
3400 Coathook Metalwork 1 2 1 @ 1200 AFFL for wheelchair users
4330 Cupboard: wardrobe Furniture/ Fitting 1 1
4391 Cupboard: special Furniture/ Fitting 1 1 to conceal medical gases; optional
6156 Dispenser: soap Furniture/ Fitting 2 1 optional
6160 Dispenser: toilet paper Furniture/ Fitting 2 1
8400 Grab rail: WC Metalwork 1 2 1 behind toilet, 1 to side; inclusion depends on operational policy
8430 Grab rail: Bath Metalwork 1 1 inclusion depends on operational policy
8450 Grab rail: Shower Metalwork 1 1 inclusion depends on operational policy
8500 Grab rail: WC, hinged Metalwork 1 1 optional; inclusion depends on operational policy
9200 Hook: for catheter bag Metalwork 1 2 inclusion depends on operational policy
10800 Hook: for IV flasks Metalwork 1 2 inclusion depends on operational policy
13700 Mirror Metalwork 1 1 over basin
16250 Oxygen flowmeter Furniture/ Fitting 3 1 optional
20055 Partitions: shower Furniture/ Fitting 1 1
20650 Soap/ shampoo holder Furniture/ Fitting 1 1
21950 Suction adapter Furniture/ Fitting 3 1 optional
22000 Suction bottle Furniture/ Fitting 3 1 optional
23700 Towel rail Metalwork 1 2 with grabrail strength & fixings
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to hand basin
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3031 Television: flat screen 3 1 yes ___ ___ ___ ___ ___ ___ ___ recessed in wall; provide service panel behind TV
3120 Basin: vanity 1 1 ___ ___ yes ___ yes yes yes ___
3600 Bath: spa 1 1 ___ ___ yes ___ yes yes yes ___ or adjustable height bath / island bath
47400 Shower: hand-held 1 1 ___ ___ yes ___ yes yes yes ___
47500 Shower: fixed rose 1 1 ___ ___ yes ___ yes yes yes ___ rain shower head
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ wall telephone
55605 Toilet suite: patient 1 1 ___ ___ yes ___ ___ yes yes ___
55607 Toilet suite: bidet 1 1 ___ ___ yes ___ ___ yes yes ___
ID Description Service Category Qty Selection / Remarks
1005 Voice / Data outlet: single Communications 1 to telephone
1090 TV: MATV Communications 1
4035 Floor trough Hydraulics 3 with SS grille in shower
5000 Airconditioning HVAC
5019 Exhaust HVAC for steam/ heat
6000 General fluorescent Lighting
6125 Vanity (concealed) Lighting
7000 Oxygen (O2) Medical Gases 1 optional
7040 Suction Medical Gases 1 optional
8000 Patient/ Staff call Nurse Call 3 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
9001 GPO: Double Power 1 locate near door in vestibule
9040 Body protected Power
9060 GPO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply with relevant electric safety guidelines
9060 GPO: Special: for equipment Power 1 waterproof for TV
45570471 Special: decorative Lighting
0 0