Room Code GENXR-I
Net Room Area Briefed 30
Hours of Operation Available 24 Hours
Occupancy 1 patient; 1 - 2 staff
Description / Special Requirements General X-ray is a room for undertaking general radiographic procedures, which may be located within the Imaging Unit or within an emergency care area. Additional Design Requirements: - Radiation sheilding to walls and glazing as advised by Radiation Consultant - Metal channel struts may be required to the ceiling, depending on equipment to be installed - Cable ducting between the X-ray table, vertical bucky and control area may be required, depending on equipment type and layout - 'X-ray in Use' warning lights will be required outside each entry door - Equipment and services required are to be installed to manufacturer's specifications Body Protected electrical area
Amendment 24.10.2010 First Draft 02.05.2011 Fabric, FF & Services updated 20.01.2017 Description, Fabric, FF, FE & Services updated
ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
8040 Door protection Composite Prefinished PVC To door frame
9230 Doors Solid Core Paint Double leaf, with lead shielding Patient Entry/ Exit; 1400mm (min) clear opening
4030 Wall protection Composite Prefinished PVC Corner guards to 900 AFFL as required
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, tiles or other smooth impervious finish also acceptable
9053 Doors Solid Core Prefinished Single leaf, radiation shielding Staff Entry; 920mm clear opening; optional
5030 Ceiling Plasterboard Prefinished Drop-in tiles, 600x1200 mm at 3000 mm AFFL
6025 Cornice Aluminium Powdercoat shadow line
7025 Observation Lead glass Clear Internal window to control area
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel Staff Entry to control area; 920mm clear opening; optional
ID Description Category Group Qty Selection / Remarks
150 Air flowmeter Furniture/ Fitting 3 1 to services panel
1090 Bench: laminate, free standing Furniture/ Fitting 3 1 cupboards under; optional
1465 Bracket: suction bottle Furniture/ Fitting 2 1 below services panel
1650 Chair: client Furniture/ Fitting 3 1
3350 Clock: battery operated Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6156 Dispenser: soap Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
11905 Rack: lead apron Metalwork 1 1
16250 Oxygen flowmeter Furniture/ Fitting 3 1 to services panel
21950 Suction adapter Furniture/ Fitting 3 1 to services panel
22000 Suction bottle Furniture/ Fitting 3 1 on wall bracket
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to basin
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___ taps: sensor outlet; elbow action lever taps also acceptable
54520 Telephone: handset, handsfree 3 1 ___ yes ___ ___ ___ ___ ___ ___ wall telephone
61600 IMG: bucky, chest 1 1 yes ___ ___ ___ ___ ___ ___ ___ as required
62150 IMG: console, control 1 1 yes yes ___ ___ ___ ___ ___ ___ general/digital x-ray control console
66000 IMG: X-ray table, floating top 1 1 yes ___ ___ ___ ___ ___ ___ ___
68600 Xray viewer: 1 screen 1 1 yes ___ ___ ___ ___ ___ ___ ___ optional if using digital imaging systems
66600 IMG: X-ray unit, general purpose 1 1 yes ___ ___ ___ ___ ___ ___ ___
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 to control area
1040 Intercom Communications 1 to control area
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6110 Downlights: dimmable Lighting
7000 Oxygen (O2) Medical Gases 1 patient services panel
7020 Medical Air (MA) Medical Gases 1 patient services panel, optional
7040 Suction Medical Gases 1 patient services panel
8010 Staff/ Nurse assist call Nurse Call 1 patient services panel
8080 Emergency call Nurse Call 1 patient services panel
9000 GPO: Single Power 3 2-patient services panel; 1-X-ray viewer (iotional)
9001 GPO: Double Power 4 walls
9010 GPO: Emergency power, single Power 2 2-patient services panel
9040 Body protected Power
9060 GPO: Special: for equipment Power 2 Xray Equipment, chest bucky
12030 Lead lining Shielding to walls and doors as specified
1005 Voice / Data outlet: single Communications 1 wall telephone