Room Code HYDP-I
Net Room Area Briefed 90
Hours of Operation 7am to 8pm, daily
Occupancy Up to 12
Description / Special Requirements Hydrotherapy Pool for patient rehabilitation and exercise under supervision. Pool size 15m x 6 m (not including pool surrounds) provides space for up to 12 Users. Additional area required may be based on 2m2 per person. Pool and surrounds to comply with relevant standards and Guidelines. Pool will require wheelchair and trolley access. Additional privacy is required for changing and showering of patients on trolleys. Additional Design Considerations: - Depth 0.9 metres to 1.5 metres - gradual slope; Deep end may be reduced if paediatric use is likely to be frequent - Wet deck - single channel recommended; - Temperature of water recommended: 33 - 40 degrees C; - Temperature of air to be no more than 10 degees below water temperature, range 22 - 27 degrees C - Water to be earthed - Pool surface - tiled, non-slip; ensure a high level of slip resistance to tiles on the ramp; vertical surfaces of tiling do not need to be slip resistant - Glazing to pool walls recommended - Ramp access with handrail & stair access with handrails - Pool handrails required - not recessed type - Pool blanket may be required (insulation for energy conservation) - Disinfection system is essential & to be considered - Pool hydraulic hoist may be required - Underwater pressure jets for therapeutic purposes is optional
Amendment 24.10.2010 First Draft 02.05.2011 Fabric updated 11.04.2017 Description, FF & Services updated
ID Fabric Material Finish Specification Selection Remarks
1175 Floor finish Tiles Non-slip Ceramic appropriate tiles for pools should be specified
3090 Wall finish Tiles Glazed
2145 Skirting Tiles To match floor Coved
5040 Ceiling Fibre cement Paint, washable Flush set, suspended 4250AFFL recommended for ventilation & evaporation
4030 Wall protection Composite Prefinished PVC Corner guards to 900AFFL as required
9001 Doors Solid Core Paint Single leaf to Change Rooms/ Cleaner/ Plant areas; 920mm clear opening; lockable
6025 Cornice Aluminium Powdercoat shadow line
9120 Doors Alum/ Safety glass Powdercoat/ paint 1 1/2 leaf, fully glazed to Lobby/ Waiting & Exit; 1500mm clear opening, lockable, restricted access
7030 Observation Alum/ Glass Powdercoat Internal window, door height observation windows as required
7001 Windows Desirable
9003 Doors Alum/ Safety glass Powdercoat/ paint Single leaf, fully glazed alternative Exit if required by Building Regulation; 920mm clear opening, lockable
ID Description Category Group Qty Selection / Remarks
1000 Bench seat Furniture/ Fitting 1 1 to concourse, under lockers, optional
3350 Clock: battery operated Furniture/ Fitting 3 1
4800 Curtain track: shower Metalwork 1 1 to poolside shower bay
5300 Curtain: shower Furniture/ Fitting 3 1 to poolside shower bay
12600 Locker: 4 tier (1/4 size) Furniture/ Fitting 3 8 to concourse, on bench seat, optional
18800 Trolley: resuscitation, adult Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
15500 Defibrillator 3 1 yes ___ ___ ___ ___ ___ ___ ___ on resuscitation trolley
40630 Pool blanket: auto operated 1 1 yes ___ ___ ___ ___ ___ ___ ___ optional
41910 Public address system 1 1 yes ___ ___ ___ ___ ___ ___ ___ announcements, music
ID Description Service Category Qty Selection / Remarks
1140 Public address system Communications 1
4010 Cold water: outlet Hydraulics 1 for washing down concourse
4033 Floor waste Hydraulics every 3-4 metres on concourse
5005 Air conditioning: special HVAC to prevent condensation; ensure all ductwork & grilles are corrosion resistant
6000 General fluorescent Lighting to avoid reflection on water; avoid luminaires over actual water area (for maintenance)
8080 Emergency call Nurse Call 4 waterproof, chlorine resistant; 1 each side of pool
9000 GPO: Single Power 4 waterproof, chlorine resistant; 1 each side of pool
9060 GPO: Special: for equipment Power 1 motorised pool blanket if required
5050 Pressure: negative HVAC in relation to adjacent areas
5080 Humidity control HVAC
0 0