Lounge - Patient, 20m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Room Code LNPT-20-I
Net Room Area Briefed 20
Hours of Operation 24 Hours
Occupancy Up to 8 patients/ visitors; 1-2 staff intermittently
Description / Special Requirements The Patient Lounge provides a change of environment away from clinical areas for patients and visitors. It is an area where family groups can visit and patients can socialise. An external outlook is essential. Acoustics: Sound attenuation level - Medium; Acoustic privacy required. Body Protected electrical area
Amendment 24.10.10 - First Draft 21.04.11 - Room Fabric and FE modified 30.10.14 - Room Fabric, FF and Services modified
ID Fabric Material Finish Specification Selection Remarks
9115 Doors Solid Core/ Glass Paint 1 1/2 leaf, half glazed 920mm/ 1400mm clear opening, small door leaf optional if doors provided; doors are optional
8040 Door protection Composite Prefinished PVC To door frame if doors provided
5060 Ceiling Acoustic Prefinished Drop-in tiles, 600x1200
3000 Wall finish Paint Acrylic, washable
7001 Windows essential
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL if doors provided
1088 Skirting Timber Paint 150mmH x 20mm thick nominal
6030 Cornice Aluminium Powdercoat 24mm shadow angle
2878 Floor finish Carpet Nylon Broadloom carpet and vinyl also acceptable
ID Description Category Group Qty Selection / Remarks
350 Artwork Furniture/ Fitting 3 2 optional
1300 Bookcase Furniture/ Fitting 3 1 optional
2000 Chair: lounge Furniture/ Fitting 3 7 with space for wheelchair
2899 Blind: roller Furniture/ Fittings 1 1
22800 Table: low Furniture/ Fitting 3 1
23410 Bracket: television, wall mount Metalwork 3 1 for flat screen TV
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3031 Television: flat screen 3 1 yes ___ ___ ___ ___ ___ ___ ___ on bracket, optional
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ on table, optional
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
1090 TV: MATV Communications 1 optional
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
9000 GPO: Single Power 1 TV, optional
9040 Body protected Power
9001 GPO: Double Power 3
Other Documents
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. $2.99
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99