Room Code OR-CT-I
Net Room Area Briefed 50
Hours of Operation Available 24 Hours
Occupancy 1 patient; up to 3 staff assisting
Description / Special Requirements An aseptic environment for CT scanning which can be used during surgical procedures. The CT procedure room may be accessed from the adjacent Operating Room or from Operating Room corridor. The CT Gantry will move between the OR and the CT on floor tracks. The CT procedure room will be adjacent to a Control Room and Computer Room. Acoustics: Acoustic privacy is required Body Protected electrical area Additional Design Considerations: - Radiation shielding as advised by Radiation Consultant - Unistrut ceiling able to carry moving loads may be required - Cable ducts between Control Room and Computer Room may be required - 'X-ray in Use' lights are required outside each entry door - Power should be on emergency supply
Amendment 24.10.10, - First Draft
ID Fabric Material Finish Specification Selection Remarks
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL Equal to 'Acrovyn'
8040 Door protection Composite Prefinished PVC To door frame Equal to 'Acrovyn'
9232 Doors Solid Core/ Glass Paint Double leaf, with lead sheilding, lead glass observation panel Clear opening to allow CT Gantry to move from CT Room to OR
7026 Observation Lead Glass Clear Through door/s with sliding cover
3038 Wall finish Vinyl Prefinished Wall vinyl to 900AFFL
8001 Door protection Vinyl Prefinished To 900AFFL
6015 Cornice Plasterboard Paint Flush coved between wall & ceiling
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
7025 Observation Lead glass Clear Internal window to control room
9052 Doors Solid core/ Lead glass Paint 1 1/2 leaf, observation panel, lead shielding 1500mm clear
ID Description Category Group Qty Selection / Remarks
150 Air flowmeter Furniture/ Fitting 3 2
1465 Bracket: suction bottle Furniture/ Fitting 2 2
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 near door
16250 Oxygen flowmeter Furniture/ Fitting 3 4
21950 Suction adapter Furniture/ Fitting 3 4
22000 Suction bottle Furniture/ Fitting 3 4
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to basin
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
9700 Clock: analogue, electric 1 1 yes ___ ___ ___ ___ ___ ___ ___
66500 IMG: CT Scanning unit 3 1 yes yes ___ ___ ___ ___ ___ ___
68700 Xray viewer: 2 screen 1 1 yes ___ ___ ___ ___ ___ ___ ___ recessed
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 to services panel
1017 Hospital LAN Communications 1 to services pendant
1040 Intercom Communications 1 handsfree to control room
1379 Audio/ Video outlet Communications 1 to services pendant
5005 Air conditioning: special HVAC HEPA filtered
5040 Pressure: positive HVAC
6000 General fluorescent Lighting
6076 Special: 'X-ray In Use' lights Lighting 1 outside room entries
6110 Downlights: dimmable Lighting
7000 Oxygen (O2) Medical Gases 2 to services pendant
7000 Oxygen (O2) Medical Gases 2 to services panel
7010 Nitrous Oxide (N2O) Medical Gases 1 to services panel
7010 Nitrous Oxide (N2O) Medical Gases 1 to services pendant
7020 Medical Air (MA) Medical Gases 1 to services pendant
7020 Medical Air (MA) Medical Gases 1 to services panel
7040 Suction Medical Gases 2 to services panel
7040 Suction Medical Gases 2 to services pendant
7062 Tool Air: unregulated Medical Gases 1 to services pendant
7070 Scavenge Medical Gases 1 to services panel
7070 Scavenge Medical Gases 1 to services pendant
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
9000 GPO: Single Power 1 XR Viewer
9010 GPO: Emergency power, single Power 6 to services panel
9011 GPO: Emergency power, double Power 3 to services pendant
9014 GPO: UPS, double Power 3 to services pendant
9015 GPO: Cleaner Power 1
9016 GPO: UPS, special Power 1 20 Amps; to services pendant
9017 Direct power (Essential Power), 10 amp Power 1 to services pendant
9040 Body protected Power
9060 GPO: Special: for equipment Power 1 CT equipment
11000 Wall panel Services Panels 3 patient services
12030 Lead lining Shielding to walls and doors as specified