Operating Room - Integrated Imaging

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Code OR-II-I
Net Room Area Briefed 77
Hours of Operation 24 Hours
Occupancy 1 patient; 12-15 staff
Description / Special Requirements The Operating Room - Integrated Imaging is a digital operating room with an integrated C-arm for medical imaging. The digital Operating Room integrates operating room systems, the hospital's information system e.g. Picture Archive and Communications Systems (PACS), Radiology Information System (RIS), internet access and video and audio technology. Staff will be able to access images, results and medical records via sterile touch screens. The images may be transmitted in real time which allows education and/or supervision to occur in other locations that may be an adjoining observation room, other hospital or conference facility. A Control room will be located adjacent and may serve more than one Operating Room. The Equipment/ Computer Room is to be collocated with the Operating Room. Cardiac Protected electrical area Special Air Conditioning - HEPA filtration Additional Design Considerations: - Rectangular room shape preferable - Associated rooms (control room, for example) and layout to be considered in total - Equipment supplier to be involved in room layout - Equipment may be mounted differently to the current ceiling mounted option such as floor or wall options - 'X-ray in Use' warning lights required outside exit doors - 'Laser in Use' warning lights may be required outside exit doors to room if laser is to be used - Lead shielding will be required - Unistrut Ceiling able to carry moving loads may be required - Power to Imaging equipment should be on emergency supply - All imaging control systems to be connected to UPS
Amendment
ID Fabric Material Finish Specification Selection Remarks
2523 Doors Solid Core/ Lead glass Paint Double leaf, with lead shielding, lead glass observation panel 1800mm clear opening to patient entry/exit; lead shielding as specified
9005 Doors Solid Core/ Lead glass Paint Single leaf, observation panel, lead shielding 910mm clear opening to scrub room, sterile stock & control room; lead shielding as specified
2524 Observation Lead glass Clear Through door/s with sliding cover; lead shielding as specified
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
5010 Ceiling Plasterboard Paint, washable Flush set, suspended 3000mm min height AFFL; lead shielding as specified
6015 Cornice Plasterboard Paint Flush coved between wall & ceiling
2513 Door protection Composite Prefinished PVC insert Protection plate to 900 AFFL
2514 Door Protection Composite Prefinished PVC insert To door frame
3035 Wall finish Vinyl Prefinished Wall vinyl full height
7025 Observation Lead glass Clear Internal window to Control Room
ID Description Category Group Qty Selection / Remarks
150 Air flowmeter Furniture/ Fitting 3 2 to services on pendants
300 Trolley: anaesthetic Furniture/ Fitting 3 1
1102 Bench: resinate, mobile Furniture/ Fitting 3 1 Documentation station: computers, write-up; optional
1440 Bowl stand: single Furniture/ Fitting 3 2
1580 Chair: anaesthetist Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
8390 Trolley: gowns Furniture/ Fitting 3 1
10200 Trolley: instrument Furniture/ Fitting 3 3
11100 IV stand: mobile Furniture/ Fitting 3 2
11500 Kickbucket & stand Furniture/ Fitting 3 2
12300 Linen carrier: dirty, single Furniture/ Fitting 3 2
13500 Table: mayo Furniture/ Fitting 3 1
15100 Bracket: monitor Furniture/ Fitting 3 2 to PCs on document station.
16250 Oxygen flowmeter Furniture/ Fitting 3 4 to services on pendants
19060 Safe: dangerous drugs, small Furniture/ Fitting 1 1 optional
21730 Stool: operating, mobile Furniture/ Fitting 3 2
21950 Suction adapter Furniture/ Fitting 3 4 to services on pendants
22000 Suction bottle Furniture/ Fitting 3 4 in mobile carrier
22050 Suction bottle carrier Furniture/ Fitting 3 1
24400 Whiteboard Furniture/ Fitting 2 1 optional
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2777 Monitor - LCD flat sceen 3 1 yes yes ___ ___ ___ ___ ___ ___ flush mounted, to Documentation station
2766 IMG: imaging unit C arm 2 1 yes yes ___ ___ ___ ___ ___ ___ on ceiling track or floor mounted; model TBC by project
5133 Anaesthetic machine + monitor 3 1 yes opt ___ ___ ___ ___ ___ ___
5135 Services pendant: 1 arm, height adj 1 1 yes yes ___ ___ ___ ___ ___ ___ 1x Anaesthetic services pendant
5137 Light: operating, 2 arm, light/ monitor: LCD flat screen 2 2 yes yes ___ ___ ___ ___ ___ ___ with camera attachment to one (optional); 2 OR lights, 4 monitors
5138 Laparoscopic surgical equipment 3 1 yes yes ___ ___ ___ ___ ___ ___ Insufflator, light source, camera controller/ processor, video monitor; optional
5136 Camera: OR light attachment (surgical field) 2 1 yes yes ___ ___ ___ ___ ___ ___ optional
5134 Clock: slave, dual theatre/ elapsed time 1 1 yes ___ ___ ___ ___ ___ ___ ___ master clock system
5980 Services pendant: 2 arm, height adj; 1a, 1b 1 1 yes yes ___ ___ ___ ___ ___ ___ 1x Anaesthetic services pendant; 1x Surgical equipment pendant
6468 Camera: in room 2 1 yes yes ___ ___ ___ ___ ___ ___ CCTV
7241 Surgical plume extractor 3 1 yes ___ ___ ___ ___ ___ ___ ___ consider either a mobile unit or extractor integrated into surgical pendant
5794 Operating table: electric 3 1 yes ___ ___ ___ ___ ___ ___ ___ Table type TBC by project - fixed or mobile
11400 Computer: PC & monitor 3 2 yes yes ___ ___ ___ ___ ___ ___ for nursing & medical staff
16000 Diathermy machine 3 1 yes ___ ___ ___ ___ ___ ___ ___
28301 Pump: infusion, single 3 2 yes ___ ___ ___ ___ ___ ___ ___ Qty TBC by project
39530 Patient warming device 3 1 yes ___ ___ ___ ___ ___ ___ ___ Type TBC by project
53850 Pump: syringe 3 2 yes ___ ___ ___ ___ ___ ___ ___ Qty TBC by project
54520 Telephone: handset, handsfree 3 1 ___ yes ___ ___ ___ ___ ___ ___ on wall
55750 Torniquet: surgical 3 1 yes ___ ___ ___ ___ ___ ___ ___ mobile
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 to documentation station; 1 outlet for telephone, optional
7000 Oxygen (O2) Medical Gases 6 2-Anaesthetic pendant-each, 2-Surgical pendant
7010 Nitrous Oxide (N2O) Medical Gases 3 1-Anaesthetic pendant-each, 1-Surgical pendant
7020 Medical Air (MA) Medical Gases 3 1-Anaesthetic pendant-each, 1-Surgical pendant
7040 Suction Medical Gases 6 2-Anaesthetic pendant-each, 2-Surgical pendant
7050 Gas Alarm Panel Medical Gases 1 wall mounted, to wall services panel 1
7070 Scavenge Medical Gases 3 1-Anaesthetic pendant-each, 1-Surgical pendant
1951 Staff assist call Nurse Call 1 + indicator button & light; to wall services panel 2
8080 Emergency call Nurse Call 1 + indicator button & light; to wall services panel 2
8090 Orderly/ Porter call Nurse Call 1 optional; to wall services panel 2
9000 GPO: Single Power 12 to services pendants; 4-Anaesthetic pendant-each, 4-Surgical pendant
9010 GPO: Emergency power, single Power 18 to services pendants; 6-Anaesthetic pendant-each, 6-Surgical pendant
7030 Tool Air Medical Gases 2 1-Surgical pendant, 1-wall services panel 1, with controls
9010 GPO: Emergency power, single Power 4 to wall services panel 1
5005 Air conditioning: special HVAC HEPA filtered
5040 Pressure: positive HVAC
6001 General: colour corrected Lighting variable lighting level, dimmable
9015 GPO: Cleaner Power 1 to wall
9010 GPO: Emergency power, single Power 1 for LCD screen wall monitor, optional
1120 Monitor connection facilities and cabling Communications 1 all services
6074 Special: 'Laser In Use' lights Lighting outside room entries, if laser to be used (optional)
11000 Wall panel Services Panels 2 flush mounted, wall services
1379 Audio/ Video outlet Communications 1 to documentation station
1379 Audio/ Video outlet Communications 3 to services pendants; 1-Anaesthetic pendant-each, 1-Surgical pendant (fibre-optic)
7062 Tool Air: unregulated Medical Gases 3 to services pendants; 1- each pendant for pendant brakes
9014 GPO: UPS, double Power 2 to documentation station
9011 GPO: Emergency power, double Power 4 to documentation station
2141 GPO: UPS, single Power 18 to services pendants; 6-Anaesthetic pendant-each, 6-Surgical pendant
1922 GPO: Special: 20 amp Power 1 to wall services panel 1; optional, TBC by Project
9050 Direct connection Power 6 1-clock, 3-pendants, 2-OR lights/flat panels
6200 Light switches Lighting light switches on service panel 1
9010 GPO: Emergency power, single Power 1 to wall services panel 2
9000 GPO: Single Power 2 to wall services panel 2
1007 Voice / Data outlet: triple Communications 3 to services pendants; 1-Anaesthetic pendant-each, 1-Surgical pendant
1947 Carbon Dioxide (CO2) Medical Gases 2 1 - Surgical pendant, 1-Anaesthetic pendant
1948 GPO: Single phase, high current, 32 Amp Power 1 to wall services panel 1; optional; for green light laser
1985 Voice / Data outlet: telephone Communications 1 to documentation station; wall mounted
2024 Music system Communications 1 optional
9030 Cardiac protected/ IPS Power
1085 Temperature monitor & alarm Communications 1