Room Code PBTR-H-10-I
Net Room Area Briefed 10
Hours of Operation 24 Hours
Occupancy 1 patient; 1-2 staff intermittently
Description / Special Requirements A patient Bed Bay used for holding of patients prior to procedures, observation of patients following procedures or for assessment and treatment of patients with non acute conditions. The Patient Bay will have close access to a staff handwashing basin. Body Protected electrical area
Amendment 24.10.2010 First Issue 30.05.2016 Revisions to FF, Services
ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
3092 Wall protection MDF Laminate Bed protection wall panel
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
150 Air flowmeter Furniture/ Fitting 3 1 optional, required if air outlet provided
1465 Bracket: suction bottle Furniture/ Fitting 2 1 required if suction outlet provided
2650 Chair: visitor, patient Furniture/ Fitting 3 1 optional
4600 Curtain track: bed screen Metalwork 1 1
5000 Curtain: bed screen Furniture/ Fitting 3 1
5830 Dispenser: antiseptic hand rub Furniture/ Fitting 2 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
12900 Louvred panel: for storage-bins Metalwork 1 1 optional
16250 Oxygen flowmeter Furniture/ Fitting 3 1 required if oxygen outlet provided
21755 Storage bins Furniture/ Fitting 3 3 on louvred panel, optional
21950 Suction adapter Furniture/ Fitting 3 1 required if suction outlet provided
22000 Suction bottle Furniture/ Fitting 3 1 required if suction outlet provided
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3700 Bed: inpatient, electric 3 yes ___ ___ ___ ___ ___ ___ ___ spatial provision required
31700 Light: examination, ceiling 1 1 yes ___ ___ ___ ___ ___ ___ ___
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6030 Special: downlights Lighting over bed/ trolley
7000 Oxygen (O2) Medical Gases 1 optional, dependant on use of the bay
7020 Medical Air (MA) Medical Gases 1 optional, dependant on use of the bay
7040 Suction Medical Gases 1 optional, dependant on use of the bay
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
9000 GPO: Single Power 3 to bedhead
9000 GPO: Single Power 1 to bedhead, low level for bed
9010 GPO: Emergency power, single Power 3 to bedhead
9040 Body protected Power
2430 Wall service panel Services Panels 1 as required for medical gases
2088 Light switch: single Lighting 1 at the bed head
0 0