Patient Bay - Holding, Enclosed, 12m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Code PBHE-12I
Net Room Area Briefed 12
Hours of Operation 24 Hours
Occupancy 1 patient; 1 - 2 staff intermittently
Description / Special Requirements An enclosed Patient Bed Bay used for holding patients prior to procedures, observation of patients following procedures and/or assessment and treatment of patients with non acute conditions. Each bay must be large enough to accommodate an adult bed with additional space for monitoring equipment and to ensure access for staff in case of emergency. Each bay or cubicle shall have a minimum clearance of 91.44 centimeters (3 feet) between walls or partitions and the sides and foot of stretchers or patient beds. The Enclosed Patient Bay may be used for isolation of patients and will contain a staff handwashing basin. Patient toilets and emergency equipment should be readily accessible. Body Protected electrical area
Amendment 24.10.2010 First Draft 31.01.2017 Description, Fabric, FF, FE, Services updated
ID Fabric Material Finish Specification Selection Remarks
3092 Wall protection MDF Laminate Bed protection wall panel
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
7035 Observation Alum/ Glass Powdercoat Internal window optional to front and side walls
6025 Cornice Aluminium Powdercoat shadow line
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, tiles or other smooth impervious finish also acceptable
4020 Wall protection Composite Prefinished PVC Crash rail at 900AFFL
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
7001 Windows external outlook desirable
9003 Doors Alum/ Safety glass Powdercoat/ paint Single leaf, fully glazed 1200mm clear opening, sliding, surface mounted
ID Description Category Group Qty Selection / Remarks
150 Air flowmeter Furniture/ Fitting 3 1 optional
1252 Blind: Venetian integral Furniture/ Fitting 1 1 1 to each internal and external windows as required
1465 Bracket: suction bottle Furniture/ Fitting 2 1
2650 Chair: visitor, patient Furniture/ Fitting 3 1 optional
4600 Curtain track: bed screen Metalwork 1 1
5000 Curtain: bed screen Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6156 Dispenser: soap Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
12900 Louvred panel: for storage-bins Metalwork 1 1 optional
16200 Table: overbed Furniture/ Fitting 3 1
16250 Oxygen flowmeter Furniture/ Fitting 3 1
21755 Storage bins Furniture/ Fitting 3 3 on louvred panel, optional
21950 Suction adapter Furniture/ Fitting 3 1
22000 Suction bottle Furniture/ Fitting 3 1
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to basin
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___ taps: sensor outlet; elbow action lever taps also acceptable
3700 Bed: inpatient, electric 3 yes ___ ___ ___ ___ ___ ___ ___ spatial provision required
31700 Light: examination, ceiling 1 1 yes ___ ___ ___ ___ ___ ___ ___ optional, depending on use of the bay
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC
6001 General: colour corrected Lighting dimmable for night lighting
7000 Oxygen (O2) Medical Gases 1
7020 Medical Air (MA) Medical Gases 1 optional
7040 Suction Medical Gases 1
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
9000 GPO: Single Power 3 to bedhead
9000 GPO: Single Power 1 to bedhead, low level for bed
9010 GPO: Emergency power, single Power 3 to bedhead, & cardiac monitor
9015 GPO: Cleaner Power 1
9040 Body protected Power
11000 Wall panel Services Panels 1 flush mounted, patient services
6030 Special: downlights Lighting 1 over bed/ trolley
0 0