Room Code RAD-BUNK-I
Net Room Area Briefed 128
Hours of Operation 8am to 8pm, daily
Occupancy 1 patient, up to 4 staff
Description / Special Requirements The Radiotherapy Bunker room will contain a medical linear accelerator used used primarily to treat cancer. The Linear Accelerator uses a high energy radiation beam to localise treatment on a tumour. Radiation sheilding will be required, most commonly concrete is used as the primary sheilding material. A Control Room will be located next to to the Bunker Room. Additional Design Requirements: - Radiation sheilding to walls and glazing as advised by Radiation Consultant - Laser positioning lights will be required to manufacturers details - 'Beam on' Warning lights will be required at room entrance Body Protected electrical area
Amendment 24.10.1200 - First Draft 21.04.2011 - Room Fabric and FF modified 29.05.2014 - General amendments to Fabric, FF, FE and Services
ID Fabric Material Finish Specification Selection Remarks
8040 Door protection Composite Prefinished PVC To door frame
9001 Doors Solid Core Paint Single leaf to Linac Equipment 850mm clear opening. Door Hardware E. Refer to HIDRFG, part C, DOORS
1045 Floor finish Vinyl, non slip Textured Seamless, coved around basin
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
3065 Wall finish Laminate Prefinished Splashback to basin
4031 Wall protection Composite Prefinished PVC Corner guards to 1500AFFL as required
5030 Ceiling Plasterboard Prefinished Drop-in tiles, 600x1200 mm allows access to in-ceiling services
6025 Cornice Aluminium Powdercoat shadow line
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1 L shaped
4410 Cupboard: under bench Furniture/ Fitting 1 2 under bench, 2 sides
4430 Cupboard: drawer unit Furniture/ Fitting 1 1 under bench, storage
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 to basin
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6156 Dispenser: soap Furniture/ Fitting 2 1 to sink
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1
20000 Shelving unit: adjustable Furniture/ Fitting 1 1 over bench, 1 side
20012 Shelving unit: fixed shelves Furniture/ Fitting 1 1 tray and block storage
23410 Bracket: television, wall mount Metalwork 1 1
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to basin
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2022 Positioning laser: radiotherapy 3 5 yes ___ ___ ___ ___ ___ ___ ___ final qty as per manufacturer's specifications, usuall between 2-5
3031 Television: flat screen 3 1 yes ___ ___ ___ ___ ___ ___ ___ wall mounted
3100 Basin: scrub, Type A 1 1 ___ ___ yes ___ yes yes yes ___
7300 Camera: CCTV security 1 2 yes ___ ___ ___ ___ ___ ___ ___ to view patient
33300 Linear accelerator 2 1 yes ___ ___ ___ ___ ___ ___ ___ services according to manufacturer's specifications
35950 Monitor 3 2 yes opt ___ ___ ___ ___ ___ ___ in-room monitor
ID Description Service Category Qty Selection / Remarks
1005 Voice / Data outlet: single Communications 1 TV monitor
1006 Voice / Data outlet: double Communications 3 wall mounted, 1 outlet for telephone
1040 Intercom Communications 1 handsfree, for patient communication
2001 Emergency Stop button Power 6 one in corridor
2043 Last Person Out Button Communications 2 one inside bunker and one at entrance
6001 General: colour corrected Lighting
6076 Special: 'X-ray In Use' lights Lighting 1
6095 Special: "Beam On" lights Lighting 1
6110 Downlights: dimmable Lighting
6200 Light switches Lighting to room and dimmable lights
9000 GPO: Single Power 6 to positioning lasers, wall mounted. again depending on requirements 2-5
9001 GPO: Double Power 4 above bench
9001 GPO: Double Power 4 on walls
9015 GPO: Cleaner Power 1
9040 Body protected Power
9060 GPO: Special: for equipment Power linear accelerator, according to manufacturer's specifications
5000 Airconditioning HVAC