Seclusion Room

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Room Code SECL-I
Net Room Area Briefed 12
Hours of Operation 24 Hours
Occupancy 1 patient; 1-2 staff intermittently
Description / Special Requirements A Seclusion Room provides for the sole confinement of a distressed or agitated person requiring separation for short periods at any hour of the day or night on an involuntary basis. The Seclusion Room will be observable from the Staff Station. An external outlook is desirable. All glazing (including external windows) must comply to relevant safety standard. Acoustics: Sound attenuation level high; Acoustic privacy is required Additional Design Considerations: - An internal observation window is required - A second room egress door is required
Amendment 24.10.10, - First Draft 21.04.11, - Outline specifications and FF modified
ID Fabric Material Finish Specification Selection Remarks
1010 Floor finish Vinyl Cushioned Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
7015 Observation Safety glass Clear Through door/s
3072 Wall finish Vinyl Cushioned Wall vinyl full height
7045 Observation Safety glass Powdercoat Internal window double glazed with integral venetians, optional
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
7001 Windows external windows double glazed safety glass with integral venetians
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 1150mm clear opening, lockable from outside. with integral blinds
6010 Cornice Plasterboard Paint 90mm to match ceiling finish
5010 Ceiling Plasterboard Paint, washable Flush set, suspended 3000 mm height
8040 Door protection Composite Prefinished PVC To door frame
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 500mm clear outward opening, optional
ID Description Category Group Qty Selection / Remarks
1252 Blind: Venetian integral Furniture/ Fitting 1 2 to window if provided, controls outside room
13350 Mattress: foam Furniture/ Fitting 3 1 foam, on floor
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
7300 Camera: CCTV security 1 1 yes ___ ___ ___ ___ ___ ___ ___ recessed in ceiling dome
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6030 Special: downlights Lighting sealed, dimmable
6060 Special: night lights Lighting high level, dimmable
9060 GPO: Special: for equipment Power 1 CCTV camera in ceiling
Other Documents
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. $2.99
0 0