Room Code SECR-14-I
Net Room Area Briefed 14
Hours of Operation 24 Hours
Occupancy Up to 2 staff
Description / Special Requirements A lockable room for security personnel to monitor surveillance equipment. Staff identity photographs may also be taken in this area. The Security Room should be located close to the Main Entrance / Emergency Unit after hours entry. The Security Room configuration may alter to suit different monitoring arrangements; refer to Security Room-Alternative for an alternative arrangement of surveillance monitors. Acoustics: Sound attenuation level - medium; Acoustic privacy required
Amendment 24.10.10, - First Draft
ID Fabric Material Finish Specification Selection Remarks
1149 Floor finish Carpet 90/10 Wool/ Nylon Broadloom, 48 oz.
3000 Wall finish Paint Acrylic, washable
7001 Windows Desirable, for surveillance of external areas
8000 Door protection Vinyl Prefinished Kickplate, 300mm high
9004 Doors Solid Core/ Glass Paint Single leaf, observation panel 920mm clear opening, lockable
7031 Observation Alum/ Safety glass Powdercoat/ paint Internal window one way glass; with communication/document slots
949496 Skirting Timber Paint 150mmH x 20mm thick, nominal
5060 Ceiling Acoustic Prefinished Drop-in tiles, 600x1200
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1
1250 Blind: Venetian Metalwork 3 1 to external window, if provided
2100 Chair: ergonomic, office Furniture/ Fitting 3 2
2600 Chair: visitor, office Furniture/ Fitting 3 1
3400 Coathook Metalwork 1 2
4230 Counter top Furniture/ Fitting 1 1 to communication window
4360 Cupboard: door ht adj. shelves Furniture/ Fitting 1 1 lockable
17360 Pinboard: fabric covered Furniture/ Fitting 1 1 above bench
18160 Projection screen: ceiling mount Furniture/ Fitting 1 1 900mmW, for photo backdrop, as required
20012 Shelving unit: fixed shelves Furniture/ Fitting 1 1 monitor chambers for CCTV monitors, optional
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 under bench
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
7500 Camera: ID photo 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional, on tripod stand
11400 Computer: PC & monitor 3 2 yes yes ___ ___ ___ ___ ___ ___ flat screen
35860 Monitor: CCTV 3 9 yes yes ___ ___ ___ ___ ___ ___ to monitor chambers, if provided
41100 Printer: networked 3 1 yes yes ___ ___ ___ ___ ___ ___
54510 Telephone: handset, standard 3 2 ___ yes ___ ___ ___ ___ ___ ___
ID Description Service Category Qty Selection / Remarks
1005 Voice / Data outlet: single Communications 9 to monitor chambers, if provided
1006 Voice / Data outlet: double Communications 1 to printer
1006 Voice / Data outlet: double Communications 2 to workstations; 1 outlet on each panel for telephone
1090 TV: MATV Communications 1
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9000 GPO: Single Power 9 to monitor chambers, if provided
9001 GPO: Double Power 5 2 per workstation +1-printer