Water Treatment Plant Room

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Room Code WTPL-I
Net Room Area Briefed 15
Hours of Operation 24 Hours
Occupancy 1 - 2
Description / Special Requirements The Water Treatment Plant Room is a lockable room for water treatment systems used in dialysis, including booster pumps, particle filters, water softeners, carbon filters and reverse osmosis systems. Refer to Manufacturer's Specifications for details of Reverse Osmosis (RO) Water Treatment Plant equipment. In particular this equipment will incorporate a heat disinfection function, and water saving features. The Water Treatment Plant Room should be located in close proximity to the Renal Dialysis Unit to permit short tubing runs to each Treatment Bay, and permit staff to monitor and service the water treatment systems. Special Design Requirements: - Ventilation, exhaust and/or airconditioning must be deisgned to accommodate the heat loads of the specified equipment. - High level sound isolation is required to ensure noise generated from this room does not invade Treatment spaces - Structural Engineer's assessment must be sought for floor load bearing capacity with respect to water treatment and pre- treatment plant equipment - Service access will be required aound the perimeter of all plant equipment - Pipework and components installed after the water inlet within this room shall not contain brass or copper
Amendment 24.10.10, - First Draft
ID Fabric Material Finish Specification Selection Remarks
1280 Floor finish Concrete Trowel Sealed
3000 Wall finish Paint Acrylic, washable
5021 Ceiling Plasterboard Paint, washable Water resistant, flush set, suspended Min Height 2400mm; Water resistant drop in tile ceiling also acceptable
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
8040 Door protection Composite Prefinished PVC To door frame
2155 Skirting Concrete Sealed Coved concrete to 150 AFFL
9110 Doors Solid Core Paint 1 1/2 leaf 1600mm clear opening, lockable
ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1 work bench
21680 Stool: adjustable, mobile Furniture/ Fitting 3 1 under bench
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
42295 Pump: pressure booster 3 2 yes ___ ___ ___ ___ ___ ___ ___ as needed to achieve required water pressure
61295 Water treatment plant 3 3 yes ___ yes ___ ___ ___ yes ___ RO Plant; details according to Manufacturer's Specifications
ID Description Service Category Qty Selection / Remarks
1002 Alarm Communications 1 to Staff Station - Renal Unit for Plant Equipment status/ malfunction
4005 Cold water Hydraulics 1 inlet for RO Water Treatment Plant Equipment
4033 Floor waste Hydraulics 1 floor waste must be capable of high flow rates and high temperature water (up to 95 degrees C) from the RO Water Plant
5000 Airconditioning HVAC A/C & exhaust system to accommodate heat loads generated by plant eqeuipment
5019 Exhaust HVAC heat extraction will be required
6000 General fluorescent Lighting
9011 GPO: Emergency power, double Power 4 for use of hand tools in the room, on a separate circuit
9060 GPO: Special: for equipment Power 1 3 phase, according to Manufacturer's specifications
9060 GPO: Special: for equipment Power 2 pumps, as required