1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code BPATH-3-I
Net Room Area Briefed 3
Hours of Operation 24 Hours
Occupancy 1-2 staff
Description / Special Requirements A Pathology Bay provides for point of care laboratory analyses in critical care areas and for preparation of contrast injections in imaging facilities. Staff use this space for specimen preparation and testing. The workspace will suit a staff member who is standing. This bay may need to accommodate a fridge for temporary storage of specimens before delivery to the main pathology laboratory. This bay may be collocated with a pneumatic tube bay. The pneumatic tube bay can be used for sending specimens to the main pathology laboratory for comprehensive analysis. Additional Design Considerations: - Staff should have ready access to a handwashing bay - Bay should be supervised by staff at all times - Spatial arrangment will depend on devices required in each clinical setting - devices to be deterimed at project level - In a multi-device bay, a 300mm gap between each device is recommended - Consider height clearances required over devices if over head joinery is installed - Consider the weight of devices and reinforce joinery as required - Demineralised water may be required to the sink depending on device requirements
Amendment 28.04.2015 First draft 22.06.2015 Description and Services modified 04.07.2016 Document amended to match RLS.

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended Acoustic tiles acceptable
5007 Ceiling Plasterboard Paint Bulkhead Laminate infill also acceptable. Between above bench joinery and ceiling.
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL Align heights of corner guards with other corridor elements
3060 Wall finish Vinyl Prefinished Splashback
6025 Cornice Aluminium Powdercoat shadow line
1000 Floor finish Vinyl Standard slip resistant Seamless, coved

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1 With optional inset sink. Length to suit layout, refer RLS or project specific requirements.
1470 Bracket: sharps Furniture/ Fitting 2 1 Optional.
4410 Cupboard: under bench Furniture/ Fitting 1 2 With adjustable shelf. Number to suit layout, refer RLS or project specific requirements.
4470 Cupboard: wall mounted, lockable Furniture/ Fitting 1 4 Over bench. Number to suit layout, refer RLS or project specific requirements.
5830 Dispenser: antiseptic hand rub Furniture/ Fitting 2 1 May not be required if Hand Hygiene Bay colocated.
5975 Waste bin: clinical Funiture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
19700 Sharps bin Furniture/ Fitting 3 1 Optional.

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
6459 Point-of-Care device 3 1 yes opt ___ ___ ___ ___ ___ ___ Number and type to be project specific.
11400 Computer: PC & monitor 3 1 yes yes ___ ___ ___ ___ ___ ___
41150 Printer: labels 3 1 yes opt ___ ___ ___ ___ ___ ___
43800 Refrigerator: under-bench, 120 Litre 3 1 yes ___ ___ ___ ___ ___ ___ ___ Local temperature monitoring. Optional, depends on frequency of collection.
47800 Sink, SS: single in bench 1 1 ___ ___ yes opt opt yes yes ___
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ Bench or wall mounted, optional.

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 4 Number depends on project specific requirements.
5000 Airconditioning HVAC consistent with adjacent area
6000 General fluorescent Lighting consistent with adjacent area
6055 Special: task light, built in Lighting Under O/H cupboards
9011 GPO: Emergency power, double Power 1
9001 GPO: Double Power 3 Number depends on project specific requirements.

Print