1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code BUT-1-I
Net Room Area Briefed 1
Hours of Operation 24 Hours
Occupancy 1
Description / Special Requirements The Utility Bay provides an area with a bench and sink for use as a preparation area. The bay may be located adjacent to patient treatment areas. The bay should be located in close proximity to a staff handwashing basin.
Amendment 24.10.2010 First Draft 06.05.2011 Room Fabric updated 18.08.2016 Services updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
4031 Wall protection Composite Prefinished PVC Corner guards to 1500 AFFL other heights also acceptable as per project standardisation
5010 Ceiling Plasterboard Paint, washable Flush set, suspended minimum height 2400mm; plasterboard drop in tile ceiling may also be used if bay is part of a larger zone
6025 Cornice Aluminium Powdercoat shadow line
3052 Wall finish Vinyl Prefinished Wall vinyl to 1500mm AFFL
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
1000 Floor finish Vinyl Standard slip resistant Seamless, coved

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1010 Bench: stainless steel Metalwork 1 1 with wet edge and inset sink, open under
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to sink
6156 Dispenser: soap Furniture/ Fitting 2 1 to sink
20000 Shelving unit: adjustable Furniture/ Fitting 1 1 over bench
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 under bench

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
47800 Sink, SS: single in bench 1 1 ___ ___ yes opt opt yes yes ___ warm water if located in a patient accessible area; with wall mounted lever taps

Services

ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 1
5000 Airconditioning HVAC consistent with adjacent area
1983 General fluorescent: downlights Lighting

Print