1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code CLCRT-I
Net Room Area Briefed 14
Hours of Operation Available 24 Hours
Occupancy Up to 3 staff
Description / Special Requirements Room adjacent to Catheter Lab Procedure Room/s with direct visibility to the patient for remote control of equipment, and review and reporting of procedure images. The Control/ Reporting room may serve two procedure rooms. Acoustics: Acoustic privacy is required Additional Design Considerations: - Radiation shielding as advised by Radiation Consultant - Cable ducts from Angiography Procedure Room and Computer/Equipment room may be required
Amendment 24.10.10, - First Draft

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
6025 Cornice Aluminium Powdercoat shadow line
9004 Doors Solid Core/ Glass Paint Single leaf, observation panel 920mm clear opening
8000 Door protection Vinyl Prefinished Kickplate, 300mm high
7025 Observation Lead glass Clear Internal window to procedure room
5060 Ceiling Acoustic Prefinished Drop-in tiles, 600x1200
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
3000 Wall finish Paint Acrylic, washable

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1 at 900H
1950 Chair: ergonomic, high Furniture/ Fitting 3 3
3400 Coathook Metalwork 1 2
17252 Pedestal drawer unit: mobile, 840mmH Furniture/ Fitting 3 1 under bench
17360 Pinboard: fabric covered Furniture/ Fitting 1 2 over bench
20000 Shelving unit: adjustable Furniture/ Fitting 1 2 for books, manuals, over bench
24400 Whiteboard Furniture/ Fitting 2 1 optional

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
11400 Computer: PC & monitor 3 1 yes yes ___ ___ ___ ___ ___ ___ flat screen
35950 Monitor 3 2 yes opt ___ ___ ___ ___ ___ ___ patient
41100 Printer: networked 3 1 yes yes ___ ___ ___ ___ ___ ___
54510 Telephone: handset, standard 3 2 ___ yes ___ ___ ___ ___ ___ ___ on bench
62150 IMG: console, control 1 1 yes yes ___ ___ ___ ___ ___ ___ Cath lab control monitors

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 6 3 outlets for telephone
1040 Intercom Communications 1 with handsfree microphone to Cath lab room
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting under O/H shelving
9001 GPO: Double Power 9
9060 GPO: Special: for equipment Power 1 Cath lab console equipment

Print