1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code ENS-ST-I
Net Room Area Briefed 5
Hours of Operation 24 Hours
Occupancy 1 patient; 1 staff assisting
Description / Special Requirements An Ensuite is for a patient to wash, shave, groom themselves, shower and use the toilet, either independently or with assistance. The area and layout must accommodate an assisting nurse, patient lifter and wheelchair access. The Ensuite may vary in configuration to suit different room types including: - Inboard Ensuite, refer to ens-st-a-i - Outboard Ensuite, refer to ens-st-b-i Acoustics: Sound attenuation level - High. Acoustic privacy required. Body Protected Electrical Area Additional Design Requirements: - The shower floor must not have a raised hob - The entrance is to be flush with the adjoining flooring - The door is to be fitted with escape hardware; a sliding door is acceptable
Amendment 24.10.2010 First Draft 05.05.2011 Services modified 29.05.2014 General amendments to FF, FE and Services 24.06.2016 General amendments to Description, FF, FE and Services

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
5023 Ceiling Plasterboard Prefinished Water resistant, drop in tiles, 600x1200 water resistant flush set plasterboard ceiling also acceptable
9001 Doors Solid Core Paint Single leaf 920 clear outward opening, privacy latch, emergency release, a sliding door is acceptable
8040 Door protection Composite Prefinished PVC To door frame
3080 Wall finish Tiles Glazed Full height to wet areas; vinyl also acceptable
2145 Skirting Tiles To match floor Coved or coved floor vinyl skirting
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
1175 Floor finish Tiles Non-slip Ceramic vinyl also acceptable
6025 Cornice Aluminium Powdercoat shadow line

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
2300 Chair: shower Furniture/ Fitting 3 1
3400 Coathook Metalwork 1 2 1 @ 1200 AFFL for wheelchair users
4800 Curtain track: shower Metalwork 1 1
5300 Curtain: shower Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1
6156 Dispenser: soap Furniture/ Fitting 2 2 1 in shower
6160 Dispenser: toilet paper Furniture/ Fitting 2 1
8400 Grab rail: WC Metalwork 1 1 may wrap around behind toilet
8450 Grab rail: Shower Metalwork 1 1
8500 Grab rail: WC, hinged Metalwork 1 1 optional
9200 Hook: for catheter bag Metalwork 1 2 optional
10800 Hook: for IV flasks Metalwork 1 2 optional
13700 Mirror Metalwork 1 1 over basin
20603 Soap/ shampoo holder: recessed Furniture/ Fitting 1 1
23700 Towel rail Metalwork 1 1 with grab rail strength and fixings
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to hand basin

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3003 Bidet handset 1 1 ___ ___ ___ ___ yes yes ___ ___ near toilet
5603 Basin: ensuite 1 1 ___ ___ yes ___ yes yes yes ___ may include a vanity; Tapware: mixer, basin mounted
8582 Bed pan flusher unit 1 1 ___ ___ yes ___ ___ ___ ___ ___ optional; toilet attachmentt, required for FGI compliance
47400 Shower: hand-held 1 1 ___ ___ yes ___ yes yes yes ___ Tapware: mixer, wall mounted
55605 Toilet suite: patient 1 1 ___ ___ yes ___ ___ yes yes ___

Services

ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 1
5000 Airconditioning HVAC
5019 Exhaust HVAC for steam/ heat
6000 General fluorescent Lighting
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
9001 GPO: Double Power 1 for hair dryer & shaver use only; to comply with relevant electric safety guidelines
9040 Body protected Power
8000 Patient to Staff call Nurse Call 2 + indicator button & light; 1-shower, 1-toilet

Print