1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code ECL-SP-I
Net Room Area Briefed 8
Hours of Operation 24 Hours
Occupancy 1 - 2
Description / Special Requirements The Clean-up/ Sub Pathology room is used for rinsing and cleaning of equipment used in the Unit, and for satellite pathology equipment such as a blood gas analyser for urgent blood testing. The room may be located in a Critical Care Unit.
Amendment 24.10.10, - First Draft

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1020 Floor finish Vinyl, non-slip Safety Seamless, coved
3000 Wall finish Paint Acrylic, washable
3052 Wall finish Vinyl Prefinished Wall vinyl to 1500mm AFFL
5023 Ceiling Plasterboard Prefinished Water resistant, drop in tiles, 600x1200
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
9004 Doors Solid Core/ Glass Paint Single leaf, observation panel 920mm clear opening
6025 Cornice Aluminium Powdercoat shadow line
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
8040 Door protection Composite Prefinished PVC To door frame

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1010 Bench: stainless steel Metalwork 1 1 with wet edge, inset sinks
4410 Cupboard: under bench Furniture/ Fitting 1 1 under SS bench
4460 Cupboard: wall mounted Furniture/ Fitting 1 1 over part SS bench
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6156 Dispenser: soap Furniture/ Fitting 2 1 to basin
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to basin

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___ Refer to BHWS-B (sim)
4650 blood gas analyser 3 1 yes ___ ___ ___ ___ ___ yes ___ optional
47850 Sink, SS: double in bench 1 1 ___ ___ yes opt opt yes yes ___ hot water

Services

ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 1
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting 1 to underside of O/H cupboards
9001 GPO: Double Power 2
9060 GPO: Special: for equipment Power 1 blood gas analyser, as required

Print