Room Code | ANRM-I |
Net Room Area Briefed | 5 |
Hours of Operation | 24 Hours |
Occupancy | 1 - 2 |
Description / Special Requirements | Anteroom or airlock associated with an Isolation room for maintenance of air pressurisation and for staff and visitors to change and dispose of protective gear used on entering or exit; a staff handwashing basin will be located within the room; glazing is recommended for patient visibility. Pressurisation - negative or positive depending on type of Isolation room. An air pressure monitoring device may be included to identify the room pressure. Body Protected electrical area |
Amendment | 24.10.2010 First Draft 01.09.2014 General revisions 28.10.2014 Modification to Room Fabric, FF, Services |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
3022 | Wall finish | Resinate, 6mm | Prefinished | Splashback | to basin, tiles also acceptable; splashback material to comply with Infection Control Guidelines | |
6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900 AFFL | ||
9007 | Doors | Solid Core/ Safety glass | Paint | Single leaf, half glazed | 920mm clear opening, self closer |
ID | Description | Category | Group | Qty | Selection / Remarks |
3400 | Coathook | Metalwork | 1 | 2 | on wall |
5578 | Trolley: PPE | Furniture/ Fitting | 3 | 1 | or joinery, dependent on Operational Policy |
5830 | Dispenser: antiseptic hand rub | Furniture/ Fitting | 2 | 1 | |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
6153 | Dispenser: moisturiser | Furniture/ Fitting | 2 | 1 | optional |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | to basin |
6158 | Dispenser: soap antiseptic | Furniture/ Fitting | 2 | 1 | to basin |
12300 | Linen carrier: dirty, single | Furniture/ Fitting | 3 | 1 | |
20015 | Shelving unit: PPE | Furniture/ Fitting | 1 | 1 | |
24100 | Waste bin: paper, 20 Litre | Furniture/ Fitting | 3 | 1 | to basin |
24125 | Waste bin: clinical | Furniture/ Fitting | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
2800 | Basin: handwash, Type B | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
40404 | Tapware: sensor | 1 | 1 | yes | ___ | yes | yes | yes | ___ | ___ | ___ | wall mounted elbow action levers also acceptable |
ID | Description | Service Category | Qty | Selection / Remarks |
5000 | Airconditioning | HVAC | no A/C provided to anteroom requiring negative pressure; exhaust only to achieve negative pressure | |
6000 | General fluorescent | Lighting | ||
5019 | Exhaust | HVAC | to negative pressure rooms | |
5015 | Ventilation | HVAC | ||
2190 | Air pressure monitoring device | HVAC | optional | |
9050 | Direct connection | Power | 1 | to sensor tap |
9015 | GPO: Cleaner | Power | 1 |