Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
![]() |
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
![]() |
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
![]() |
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. | $2.99 | |
![]() |
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. | $64.99 |
Online Room Data Sheet |
---|
Room Code | BRES-I |
Net Room Area Briefed | 1.5 |
Hours of Operation | 24 Hours |
Occupancy | N/A |
Description / Special Requirements | A recessed bay to provide supervised holding of the resuscitation trolley and equipment. The bay should be located close to a Staff Station and under staff observation. Special Design Requirements: The Bay should not impede corrior access. |
Amendment | 24.10.2010 First Draft 02.09.2014 Description, FE updated. 29.10.2014 Fabric modified. 18.08.2016 Room Fabric & Services updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
4020 | Wall protection | Composite | Prefinished PVC | Crash rail at 900AFFL | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
5007 | Ceiling | Plasterboard | Paint | Bulkhead | ||
4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500mm AFFL | other heights also acceptable as per project standardisation |
ID | Description | Category | Group | Qty | Selection / Remarks |
4460 | Cupboard: wall mounted | Furniture/ Fitting | 1 | 1 | over trolley/s, optional |
18800 | Trolley: resuscitation, adult | Furniture/ Fitting | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
5678 | ECG machine, on trolley | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
15500 | Defibrillator | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | on trolley, optional |
ID | Description | Service Category | Qty | Selection / Remarks |
5000 | Airconditioning | HVAC | consistent with adjacent area | |
9011 | GPO: Emergency power, double | Power | 2 | for recharging emergency equipment |
1983 | General fluorescent: downlights | Lighting |