Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
![]() |
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
![]() |
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
![]() |
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. | $2.99 |
Online Room Data Sheet |
---|
Room Code | PTHLB-MOD-I |
Net Room Area Briefed | 25 |
Hours of Operation | 24 Hours |
Occupancy | Up to 4 |
Description / Special Requirements | The Pathology Laboratory Module is an area consisting of modular bench and storage units for testing of specimens; the module may be suitable for Haematology, Biochemistry, Anatomical Pathology or a combination of compatible specialties. Modules may be combined to suit the operational policy and role delineation of the Unit The space may be open plan or enclosed for specialty laboratory functions such as Microbiology and Blood Bank. Each module will include a staff handwashing basin and a fixed bench with sink; all other inclusions will be modular and movable. An external outlook is desirable. |
Amendment | 24.10.10, - First Draft |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
5030 | Ceiling | Plasterboard | Prefinished | Drop-in tiles, 600x1200 mm | ||
7001 | Windows | desirable | ||||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900 AFFL | if doors provided | |
8040 | Door protection | Composite | Prefinished PVC | To door frame | if doors provided | |
9002 | Doors | Solid Core/ Glass | Paint | Single leaf, half glazed | 920mm clear opening , to adjoining module, door optional | |
9115 | Doors | Solid Core/ Glass | Paint | 1 1/2 leaf, half glazed | 1400mm clear opening, to corridor, doors optional | |
3085 | Wall finish | Tiles | Glazed | Splashback | to wet areas | |
6025 | Cornice | Aluminium | Powdercoat | shadow line |
ID | Description | Category | Group | Qty | Selection / Remarks |
1030 | Bench: resinate | Furniture/ Fitting | 1 | 1 | with inset sink, open under part |
1102 | Bench: resinate, mobile | Furniture/ Fitting | 3 | 4 | laboratory modules, with overshelves |
1250 | Blind: Venetian | Metalwork | 3 | 1 | to window if provided |
1950 | Chair: ergonomic, high | Furniture/ Fitting | 3 | 2 | |
4460 | Cupboard: wall mounted | Furniture/ Fitting | 1 | 1 | over sink bench |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | to basin |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | to basin |
17252 | Pedestal drawer unit: mobile, 840mmH | Furniture/ Fitting | 3 | 5 | under modular benches |
17262 | Pedestal cupboard unit: mobile, 840mmH | Furniture/ Fitting | 3 | 1 | under modular benches |
19820 | Shelf: SS, under | Metalwork | 1 | 1 | under part of sink bench |
24100 | Waste bin: paper, 20 Litre | Furniture/ Fitting | 3 | 1 | to basin |
24125 | Waste bin: clinical | Furniture/ Fitting | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
2800 | Basin: handwash, Type B | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | refer to BHWS-B (sim) |
11400 | Computer: PC & monitor | 3 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional |
22150 | Cabinet: fume | 1 | 2 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional, as required |
44700 | Refrigerator: laboratory | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | underbench, optional, temp alarm |
47800 | Sink, SS: single in bench | 1 | 1 | ___ | ___ | yes | opt | opt | yes | yes | ___ | hot water |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 4 | 2 outlets for telephone |
5000 | Airconditioning | HVAC | ||
6000 | General fluorescent | Lighting | ||
9000 | GPO: Single | Power | 3 | 2 to sink bench, 1 to U/B fridge |
9001 | GPO: Double | Power | 7 | shared between lab bench modules |
9060 | GPO: Special: for equipment | Power | 4 | for fume cabinets, fridge or other lab equipment as required |