| Edit it in Health Facility Briefing System (HFBS) | |||
|---|---|---|---|
|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing | |
| Room Layout Sheet | |||
|---|---|---|---|
|
|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
| Other Files | |||
|---|---|---|---|
|
|
Buy an editable Revit Room Layout Sheet (RLS) for this standard component. | $64.99 | |
| Online Room Data Sheet |
|---|
| Room Code | PBTR-R-I |
| Net Room Area Briefed | 28 |
| Hours of Operation | 24 Hours |
| Occupancy | 1 patient; 4 - 5 staff |
| Description / Special Requirements | A Patient Bed Bay for assessment, resuscitation and treatment of patients with critical conditions, located within the Emergency Unit. The Bay may have partition side walls and a bench used for preparation and write-up. Resuscitation and diagnostic equipment should be located in close proximity which may include ventilator, cardiac pacemaking equipment and mobile X-ray machine. Cardiac Protected electrical area |
| Amendment | 24.10.2010 First Draft 01.09.2022 FF, FE & Services updated 02.09.2022 Cornice updated to Aluminium shadow line 03.09.2023 RDS updated |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 3022 | Wall finish | Resinate, 6mm | Prefinished | Splashback | to basin & above bench, other smooth impervious finish also acceptable | |
| 4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500mm AFFL | as required; other heights also acceptable as per project standardisation | |
| 5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
| 3000 | Wall finish | Paint | Acrylic, washable | |||
| 2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
| 4020 | Wall protection | Composite | Prefinished PVC | Crash rail at 900mm AFFL | as required | |
| 1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
| 6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
| 5007 | Ceiling | Plasterboard | Paint | Bulkhead |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 8291 | Air flowmeter | MEQ - General | 3 | 2 | to patient supply unit |
| 1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 | open under part |
| 8404 | Bracket: sharps disposal | MEQ - General | 2 | 1 | on trolley |
| 1950 | Chair: ergonomic, high | Furniture/ Fitting | 3 | 1 | for staff use |
| 4375 | Cupboard: medication, lockable | Furniture/ Fitting | 1 | 1 | with drug safe |
| 4410 | Cupboard: under bench | Furniture/ Fitting | 1 | 1 | adjustable shelf |
| 4470 | Cupboard: wall mounted, lockable | Furniture/ Fitting | 1 | 1 | over bench, drug storage |
| 4600 | Curtain track: bed screen | Metalwork | 1 | 1 | |
| 5000 | Curtain: bed screen | Furniture/ Fitting | 3 | 1 | |
| 6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
| 6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
| 6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | to basin |
| 6158 | Dispenser: soap antiseptic | Furniture/ Fitting | 2 | 1 | to basin |
| 10700 | IV hanger for ceiling track | Metalwork | 1 | 1 | optional, may be attached to patient supply unit |
| 11200 | IV track: ceiling mounted | Metalwork | 1 | 1 | optional |
| 8309 | Oxygen flowmeter | MEQ - General | 3 | 2 | to patient supply unit |
| 8296 | Bowl stand: single | MEQ - General | 3 | 2 | |
| 8297 | Bracket: suction bottle | MEQ - General | 2 | 2 | to patient supply unit |
| 8302 | Diagnostic set: portable | MEQ - General | 3 | 1 | |
| 8306 | IV pole: mobile | MEQ - General | 3 | 1 | |
| 8318 | Suction adapter | MEQ - General | 3 | 2 | to patient supply unit |
| 8321 | Suction bottle | MEQ - General | 3 | 2 | to patient supply unit |
| 8348 | Cabinet: storage, medication, narcotics | MEQ - Furniture | 2 | 1 | in cupboard |
| 8398 | Trolley: resuscitation | MEQ - Furniture | 3 | 1 | |
| 8406 | Sharps disposal: on trolley, 11L | MEQ - General | 3 | 1 | |
| 8408 | Kick bucket | MEQ - General | 3 | 1 | |
| 8411 | Stool: adjustable, OR | MEQ - Furniture | 3 | 2 | |
| 8593 | Bracket: patient monitor | MEQ - General | 2 | 1 | |
| 8607 | Waste bin: clinical, 50 litres | MEQ - Furniture | 3 | 1 | |
| 8616 | Trolley: procedure | MEQ - Furniture | 3 | 1 | |
| 8976 | Stretcher: radiography/ trauma | MEQ - Furniture | 3 | 1 | |
| 10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 | |
| 20000 | Shelving unit: adjustable | Furniture/ Fitting | 1 | 1 | over bench, storage |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 3100 | Basin: scrub, Type A | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | refer to BHWS-A (sim) |
| 9700 | Clock: analogue, electric | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 9800 | Clock: time elapse | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | beside analogue |
| 11400 | Computer: PC & monitor | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | to bench, optional |
| 8767 | Defibrillator: with monitor | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | on resuscitation trolley |
| 9017 | Analyser: blood gas, point-of-care, 30 samples/hr | 3 | 1 | opt | opt | ___ | ___ | ___ | ___ | ___ | ___ | optional |
| 8472 | Infusion pump: syringe | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8473 | Infusion pump: rapid, blood/ solution warming, on stand | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
| 8485 | Monitor: physiologic, critical care | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8786 | Supply unit: ceiling, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8973 | Pump: suction/ aspirator, portable | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8989 | Infusion pump: single channel | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 9004 | Ventilator: transport | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 9012 | Ultrasound scanning unit: point-of-care | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional |
| 9056 | Refrigerator: drugs, under-bench, 150L | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 30288 | Light: surgical, single, ceiling | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 40404 | Tapware: sensor | 1 | 1 | yes | ___ | yes | yes | yes | ___ | ___ | ___ | |
| 54520 | Telephone: handset, handsfree | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | to bench |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 1006 | Voice / Data outlet: double | Communications | 4 | 2- patient supply unit ; 2-bench |
| 5000 | Airconditioning | HVAC | ||
| 6001 | General: colour corrected | Lighting | ||
| 6055 | Special: task light, built in | Lighting | under O/H shelves/ cupboards | |
| 7000 | Oxygen (O2) | Medical Gases | 2 | to patient supply unit |
| 7010 | Nitrous Oxide (N2O) | Medical Gases | 2 | to patient supply unit |
| 7020 | Medical Air (MA) | Medical Gases | 2 | to patient supply unit |
| 7040 | Suction | Medical Gases | 2 | to patient supply unit |
| 7070 | Scavenge | Medical Gases | 2 | to patient supply unit |
| 8000 | Patient to Staff call | Nurse Call | 1 | + indicator button & light |
| 8005 | Patient call handset | Nurse Call | 1 | call button on the handset |
| 8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
| 8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
| 2578 | PO: Emergency power, double | Power | 4 | 1- resuscitation equipment; 3- walls |
| 2576 | PO: Cleaner | Power | 1 | |
| 9030 | Cardiac protected/ IPS | Power | ||
| 2233 | Direct connection: Emergency power | Power | 2 | 1- tapware sensor; 1- patient supply unit |
| 6829 | PO: Isolated Power Suppy (IPS), single | Power | 16 | to patient supply unit |
| 2234 | Direct connection: Uninterrupted power | Power | 1 | 1- surgical light |
| 1005 | Voice / Data outlet: single | Communications | 1 | 1- under-bench refrigerator |
| 2578 | PO: Emergency power, double | Power | 4 | 1- under-bench refrigerator; 3- bench |
| 2761 | Direct connection: Tool Air | Medical Gases | 1 | to patient supply unit (for brakes) |