Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
1BR-SP-B-28-I
Net Room Area Briefed
28
Hours of Operation
24 Hours
Occupancy
1 patient; 1-2 visitors, 1-2 staff intermittently
Description / Special Requirements
A 1 Bed Room - Special, Coronary Care will accommodate one patient for the delivery of cardiac care treatment. Glazed doors and partition walls are recommended for patient visibility and privacy. Natural light and outlook is essential; the room requires the ability to view out of the window from either the chair or bed.
Acoustics: Acoustic privacy is required.
Body Protected Electrical Area
Amendment
24.10.10, - First Draft
13.04.11, - FF & Services modified
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
Carpet also acceptable
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
Timber skirting if carpeted
3000
Wall finish
Paint
Acrylic, washable
3092
Wall protection
MDF
Laminate
Bed protection wall panel
7001
Windows
Natural light & outlook essential.
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900 AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
9110
Doors
Solid Core
Paint
1 1/2 leaf
1400mm clear opening; latch set, observation panel optional
6025
Cornice
Aluminium
Powdercoat
shadow line
3067
Wall finish
Laminate
Prefinished
wall panels
7055
Observation
Alum/ Glass
Powdercoat
Internal window, double glazed
with integral venetian blinds
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
1045
Floor finish
Vinyl, non slip
Textured
Seamless, coved
under basin
4045
Wall protection
Timber
Clear finish
Corner guards
Where required
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
150
Air flowmeter
Furniture/ Fitting
3
1
Medical air
1252
Blind: Venetian integral
Furniture/ Fitting
1
1
to internal window
1465
Bracket: suction bottle
Furniture/ Fitting
2
2
1480
Bracket: ECG monitor
Furniture/ Fitting
3
1
2050
Chair: lounge, sofa bed
Furniture/ Fitting
3
1
optional
2150
Chair: patient
Furniture/ Fitting
3
1
2650
Chair: visitor, patient
Furniture/ Fitting
3
1
4330
Cupboard: wardrobe
Furniture/ Fitting
1
1
4391
Cupboard: special
Furniture/ Fitting
1
1
for refrigerator
4600
Curtain track: bed screen
Metalwork
1
1
4900
Curtain track: window
Metalwork
1
1
5000
Curtain: bed screen
Furniture/ Fitting
3
1
5410
Curtain: window, drapes
Furniture/ Fitting
3
1
set
5910
Desk: built in
Furniture/ Fitting
1
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
near basin
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6156
Dispenser: soap
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
12450
Locker: bedside
Furniture/ Fitting
3
1
mobile, 2 lockable drawers
16200
Table: overbed
Furniture/ Fitting
3
1
16250
Oxygen flowmeter
Furniture/ Fitting
3
2
19800
Shelf: laminate
Furniture/ Fitting
1
1
for flowers
21950
Suction adapter
Furniture/ Fitting
3
2
22000
Suction bottle
Furniture/ Fitting
3
2
23410
Bracket: television, wall mount
Metalwork
1
1
flat screen TV
24100
Waste bin: paper, 20 Litre
Furniture/ Fitting
3
1
to basin
24604
Window seat: built-in
Furniture/ Fitting
1
1
with drawers under
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
refer to BHWS-B (sim)
3031
Television: flat screen
3
1
yes
___
___
___
___
___
___
___
wall mounted
3700
Bed: inpatient, electric
3
1
yes
___
___
___
___
___
___
___
36050
Monitor: cardiac
3
1
yes
opt
___
___
___
___
___
___
may be telemetry
43800
Refrigerator: under-bench, 120 Litre
3
1
yes
___
___
___
___
___
___
___
optional
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
2
1-patient services panel; 1-desk; 1 outlet for telephone to each panel
1090
TV: MATV
Communications
1
1120
Monitor connection facilities and cabling
Communications
1
optional
5000
Airconditioning
HVAC
6001
General: colour corrected
Lighting
6050
Special: reading
Lighting
Up/down light
6060
Special: night lights
Lighting
7000
Oxygen (O2)
Medical Gases
2
7020
Medical Air (MA)
Medical Gases
1
7040
Suction
Medical Gases
2
8000
Patient/ Staff call
Nurse Call
1
+ indicator button & light
8005
Patient call handset
Nurse Call
1
call button & light switch on the handset
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
9000
GPO: Single
Power
3
1 adjacent to patient chair; 2 on walls
9000
GPO: Single
Power
1
Bedhead low level, for electric bed
9000
GPO: Single
Power
1
fridge (optional)
9001
GPO: Double
Power
1
desk
9010
GPO: Emergency power, single
Power
8
Bedhead
9015
GPO: Cleaner
Power
1
9040
Body protected
Power
9060
GPO: Special: for equipment
Power
1
TV