Operating Room/ Procedures Room for minor surgical or endoscopic procedures under local, regional or general anaesthetic in an aseptic environment. A clinical scrub basin or sink will be located immediately outside the room. Clean-up, scrub and Set-up rooms may be located in close proximity.
Cardiac Protected electrical area
Special Air Conditioning - HEPA filtration
Additional Design Considerations:
- 'Laser/XRay in use' warning lights may be required outside all exit doors to
room if laser/XRay equipment is to be used
- Lead shielding may be required depending on use of X-ray equipment;
to be assessed by Radiation Authority
- External windows desirable
Amendment
28.05.2014 - First Draft
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
7010
Observation
Glass
Clear
Through door/s
with cover, (sliding)
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900 AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
9125
Doors
Solid Core/ Glass
Paint
1 1/2 leaf, observation panel
1500mm clear opening to patient entry/exit
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3010
Wall finish
Paint
Scrub resistant
3038
Wall finish
Vinyl
Prefinished
Wall vinyl to 900 AFFL
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
6015
Cornice
Plasterboard
Paint
Flush coved between wall & ceiling
9004
Doors
Solid Core/ Glass
Paint
Single leaf, observation panel
920mm clear opening with sliding panel
1045
Floor finish
Vinyl, non slip
Textured
Seamless, coved
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
150
Air flowmeter
Furniture/ Fitting
3
2
to service pendant
300
Trolley: anaesthetic
Furniture/ Fitting
3
1
4355
Cupboard: tall
Furniture/ Fitting
1
1
4450
Cupboard: endoscope hanging
Furniture/ Fitting
1
1
4700
Curtain track: privacy screen
Metalwork
1
1
to patient entry door
5250
Curtain: privacy screen
Furniture/ Fitting
3
1
to patient entry door
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6410
Documentation Station
Furniture/ Fitting
1
1
built in
8390
Trolley: gowns
Furniture/ Fitting
3
1
10200
Trolley: instrument
Furniture/ Fitting
3
1
11100
IV stand: mobile
Furniture/ Fitting
3
1
11500
Kickbucket & stand
Furniture/ Fitting
3
1
12300
Linen carrier: dirty, single
Furniture/ Fitting
3
1
16250
Oxygen flowmeter
Furniture/ Fitting
3
2
2 To P1 (anaesthetics)
18050
Trolley: procedure
Furniture/ Fitting
3
1
procedure trolley
21730
Stool: operating, mobile
Furniture/ Fitting
3
2
to bench
21950
Suction adapter
Furniture/ Fitting
3
4
2 to P1 (anaesthetics) 2 to P2 (Endoscopy)
22000
Suction bottle
Furniture/ Fitting
3
6
4 on Carrier 2 to P1 (anesthetics)
22050
Suction bottle carrier
Furniture/ Fitting
3
1
24125
Waste bin: clinical
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
700
Anaesthetic machine
3
1
yes
___
___
___
___
___
___
___
3031
Television: flat screen
3
1
yes
___
___
___
___
___
___
___
Wall Mounted
11400
Computer: PC & monitor
3
1
yes
yes
___
___
___
___
___
___
to Doc Station bench
20250
Services pendant: endoscopy
1
1
yes
yes
___
___
___
___
___
___
P2
32650
Light: operating, single, 550 diam nominal
1
1
yes
___
___
___
___
___
___
___
35960
Monitor: anaesthetic
3
1
yes
opt
___
___
___
___
___
___
with printer, on anaesth machine
46705
Services pendant: adj height, with arm
1
1
yes
yes
___
___
___
___
___
___
P1
54520
Telephone: handset, handsfree
3
1
___
yes
___
___
___
___
___
___
wall mounted
68700
Xray viewer: 2 screen
1
1
yes
___
___
___
___
___
___
___
recessed optional
Services
ID
Description
Service Category
Qty
Selection / Remarks
1005
Voice / Data outlet: single
Communications
1
to wall phone
1006
Voice / Data outlet: double
Communications
2
To Doc Station
1120
Monitor connection facilities and cabling
Communications
1
For Cardiac monitor as required
1379
Audio/ Video outlet
Communications
2
To P2 (Endoscopy) to TV. Cabling required from P2 to TV as required.
1421
Tool Air Control Panel
Medical Gases
1
on Services Panel
1431
GPO: Essential power, double with RCD
Power
3
To Tall Cupboard
1922
GPO: Special: 20 amp
Power
1
to service panel 1
2044
Fire Services
Fire Services
if required by Fire Services Engineer
6001
General: colour corrected
Lighting
variable lighting level, dimmable
6074
Special: 'Laser In Use' lights
Lighting
3
outside Room Entries
6076
Special: 'X-ray In Use' lights
Lighting
3
outside room entries
6200
Light switches
Lighting
to room, procedure and warning lights
7000
Oxygen (O2)
Medical Gases
4
To P1 (anaesthetics)
7010
Nitrous Oxide (N2O)
Medical Gases
1
To P1 (anaesthetics)
7020
Medical Air (MA)
Medical Gases
4
2 to P1 (anaesthetics) 2 To P2 (Endoscopy)
7023
Carbon Dioxide (CO2)
Medical Gases
1
To P2 (Endoscopy)
7030
Tool Air
Medical Gases
2
To P2 (Endoscopy)
7040
Suction
Medical Gases
4
2 To P1 (anaesthetics) 2 To P2 (Endoscopy)
7050
Gas Alarm Panel
Medical Gases
1
7070
Scavenge
Medical Gases
2
To P1 (anaesthetics)
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
9000
GPO: Single
Power
2
to service panel 2
9001
GPO: Double
Power
2
to service panel 3
9010
GPO: Emergency power, single
Power
4
to services panel 1
9010
GPO: Emergency power, single
Power
12
6 to P1 (aneasthetics) 6 to P2 (Endoscopy)
9014
GPO: UPS, double
Power
4
Documentation Station;
9015
GPO: Cleaner
Power
1
9016
GPO: UPS, special
Power
1
To P2 (Endoscopy)
9017
Direct power (Essential Power), 10 amp
Power
1
To P2 (Endoscopy)
9030
Cardiac protected/ IPS
Power
9050
Direct connection
Power
5
to clocks, OR light, microscopes, XRV; refer to Manufacturers specifications