1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code LNPT-20-I
Net Room Area Briefed 20
Hours of Operation 24 Hours
Occupancy Up to 8 patients/ visitors; 1-2 staff intermittently
Description / Special Requirements The Patient Lounge provides a change of environment away from clinical areas for patients and visitors. It is an area where family groups can visit and patients can socialise. An external outlook is essential. Acoustics: Sound attenuation level - Medium; Acoustic privacy required. Body Protected electrical area
Amendment 24.10.10 - First Draft 21.04.11 - Room Fabric and FE modified 30.10.14 - Room Fabric, FF and Services modified

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
9115 Doors Solid Core/ Glass Paint 1 1/2 leaf, half glazed 920mm/ 1400mm clear opening, small door leaf optional if doors provided; doors are optional
8040 Door protection Composite Prefinished PVC To door frame if doors provided
5060 Ceiling Acoustic Prefinished Drop-in tiles, 600x1200
3000 Wall finish Paint Acrylic, washable
7001 Windows essential
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL if doors provided
1088 Skirting Timber Paint 150mmH x 20mm thick nominal
6030 Cornice Aluminium Powdercoat 24mm shadow angle
2878 Floor finish Carpet Nylon Broadloom carpet and vinyl also acceptable

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
350 Artwork Furniture/ Fitting 3 2 optional
1300 Bookcase Furniture/ Fitting 3 1 optional
2000 Chair: lounge Furniture/ Fitting 3 7 with space for wheelchair
2899 Blind: roller Furniture/ Fittings 1 1
22800 Table: low Furniture/ Fitting 3 1
23410 Bracket: television, wall mount Metalwork 3 1 for flat screen TV

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3031 Television: flat screen 3 1 yes ___ ___ ___ ___ ___ ___ ___ on bracket, optional
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ on table, optional

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
1090 TV: MATV Communications 1 optional
5000 Airconditioning HVAC
6000 General fluorescent Lighting
6046 Indirect lighting Lighting optional
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
9000 GPO: Single Power 1 TV, optional
9040 Body protected Power
9001 GPO: Double Power 3