Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
PROC-25-I
Net Room Area Briefed
25
Hours of Operation
24 Hours
Occupancy
1 patient; 2-4 staff
Description / Special Requirements
The Procedure Room may be required for the performance of procedures that do not require the full facilities of the Operating Suite. This may include suturing of wounds, dressings, administration of local anaesthesia and use of medical gases in connection with the procedures being performed. General anaesthesia will not be administered in this room.
Body Protected electrical area.
Note: If cardiac procedures such as indwelling cardiac pacing electrodes, intracardiac catheters or pulmonary catheters inserted into the ventricles are to be undertaken then the room should be Cardiac Protected.
Acoustics: Sound attenuation level - Medium. Acoustic privacy required.
Additional design considerations:
- Lead sheilding may be required depending on use of mobile imaging
equipment
- Bariatric patient treatments may require access to mobile bariatric lifter
- Provide sufficient clearances around all sides of the bed, to comply
with required Guidelines
Amendment
30.05.2016 First Issue
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
8040
Door protection
Composite
Prefinished PVC
To door frame
9125
Doors
Solid Core/ Glass
Paint
1 1/2 leaf, observation panel
1500mm clear opening, cover to glazing
9004
Doors
Solid Core/ Glass
Paint
Single leaf, observation panel
920mm clear opening, optional door to Clean Utility
1623
Splashback
Vinyl
Prefinished
to basin.
949813
Cornice
Plasterboard
Paint
Square set
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900 AFFL
3052
Wall finish
Vinyl
Prefinished
Wall vinyl to 1500mm AFFL
5007
Ceiling
Plasterboard
Paint
Bulkhead
between above bench joinery and ceiling.
1045
Floor finish
Vinyl, non slip
Textured
Seamless, coved
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
150
Air flowmeter
Furniture/ Fitting
3
1
700
Bed: inpatient, manual
Furniture/ Fitting
3
1
1050
Bench: laminate
Furniture/ Fitting
1
1
1465
Bracket: suction bottle
Furniture/ Fitting
2
2
1470
Bracket: sharps
Furniture/ Fitting
2
1
2938
Dispenser: hand gel, antibacterial
Furniture /Fitting
2
1
4360
Cupboard: door ht adj. shelves
Furniture/ Fitting
1
1
lockable; optional
4420
Cupboard: under bench, lockable
Furniture/ Fitting
1
1
adjustable shelves; optional
4470
Cupboard: wall mounted, lockable
Furniture/ Fitting
1
1
over bench, adjustable shelves; optional
4600
Curtain track: bed screen
Metalwork
1
1
to door opening
5000
Curtain: bed screen
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6156
Dispenser: soap
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
15150
Shelf: monitor
Furniture/ Fitting
1
1
or bracket, optional
16250
Oxygen flowmeter
Furniture/ Fitting
3
2
19700
Sharps bin
Furniture/ Fitting
3
1
wall mounted
21680
Stool: adjustable, mobile
Furniture/ Fitting
3
1
21950
Suction adapter
Furniture/ Fitting
3
2
22000
Suction bottle
Furniture/ Fitting
3
2
23950
Trolley
Furniture/ Fitting
3
1
instrument / procedure
24100
Waste bin: paper, 20 Litre
Furniture/ Fitting
3
1
to basin
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3100
Basin: scrub, Type A
1
1
___
___
yes
___
yes
yes
yes
___
refer to BHWS_A (sim), sensor tapware
3700
Bed: inpatient, electric
3
1
yes
___
___
___
___
___
___
___
9700
Clock: analogue, electric
1
1
yes
___
___
___
___
___
___
___
11400
Computer: PC & monitor
3
1
yes
yes
___
___
___
___
___
___
32150
Light: procedure, ceiling
1
1
yes
___
___
___
___
___
___
___
36055
Monitor: cardiac with vital signs
3
1
yes
opt
___
___
___
___
___
___
optional
43800
Refrigerator: under-bench, 120 Litre
3
1
yes
___
___
___
___
___
___
___
optional
54520
Telephone: handset, handsfree
3
1
___
yes
___
___
___
___
___
___
68700
Xray viewer: 2 screen
1
1
yes
___
___
___
___
___
___
___
recessed
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
2
outlets for telephone & PC (optional)
1120
Monitor connection facilities and cabling
Communications
1
5000
Airconditioning
HVAC
6001
General: colour corrected
Lighting
7000
Oxygen (O2)
Medical Gases
2
7020
Medical Air (MA)
Medical Gases
1
7040
Suction
Medical Gases
2
8000
Patient/ Staff call
Nurse Call
1
+ indicator button & light
8005
Patient call handset
Nurse Call
1
call button on the handset
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
9000
GPO: Single
Power
4
3-patient services panel, 1 low level for bed
9001
GPO: Double
Power
3
to bench
9010
GPO: Emergency power, single
Power
4
3-patient services panel, 1-monitor
9060
GPO: Special: for equipment
Power
2
recesssed XRV, procedure light
11000
Wall panel
Services Panels
1
patient services panel
7010
Nitrous Oxide (N2O)
Medical Gases
1
Optional; for analgesia use; not for anaesthesia
7070
Scavenge
Medical Gases
1
Optional; include if N2O is provided
9040
Body protected
Power
9010
GPO: Emergency power, single
Power
1
U/B fridge, optional
9000
GPO: Single
Power
1
clock