Toilet - Accessible

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Open HFBS
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Room Code WCAC-I
Net Room Area Briefed 6
Hours of Operation 24 Hours
Occupancy 1
Description / Special Requirements A toilet and handbasin for use by disabled persons with or without assistance. The room shall comply with relevant accessibility standards. Baby change facilities may also be located in this room. The room may be used by patients or visitors. If the Accessible Toilet is located in a patient care area the patient/ nurse call and emergency call points should be included. An Accessible toilet should be provided if it is the only toilet in the area. Additional Design Considerations: - Consideration may be given to installation of an additional small hand basin adajcent to the toilet that would allow wheelchair users to rinse and dry their hands from a seated position before transferring back onto their wheelchair, assisting with infection control. Ensure this basin does not impede wheelchair to toilet transfers or circulation space. - A shelf may be provided adjacent to the toilet for personal items. If provided, this shelf should be approximately 950mm AFFL and placed so that it will not be used as a support by semi ambulant users - WC design may be chosen to ensure flush controls are mounted on the open (transfer) side of the toilet to ensure they are reachable by a wheelchair user facing the toilet Acoustics: Sound attenuation level - High - Acoustic privacy.
Amendment 24.10.2010 First Draft 19.05.2011 Room area, Description, FE & Services Remarks modified 27.07.2015 Description and Fabric updated 18.01.2017 Fabric & Services amended
ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL both sides
9001 Doors Solid Core Paint Single leaf 920mm clear opening, privacy latch, emergency release
8040 Door protection Composite Prefinished PVC To door frame both sides
6025 Cornice Aluminium Powdercoat shadow line
5023 Ceiling Plasterboard Prefinished Water resistant, drop in tiles, 600x1200 mm set water resistant plasterboard ceiling also acceptable
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, or other smooth impervious finish also acceptable
1025 Floor finish Vinyl, non slip Studded Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
ID Description Category Group Qty Selection / Remarks
390 Baby change table Furniture/ Fitting 1 1 optional
3400 Coathook Metalwork 1 2 1 @ 1200 AFFL for wheelchair users
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to handbasin
6156 Dispenser: soap Furniture/ Fitting 2 1 to handbasin
6160 Dispenser: toilet paper Furniture/ Fitting 1 1
8420 Grab rail: WC, disabled use Metalwork 1 2
13700 Mirror Metalwork 1 1
19100 Waste bin: sanitary Furniture/ Fitting 3 1
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to handbasin
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3003 Bidet handset 1 1 ___ ___ ___ ___ yes yes ___ ___
5604 Toilet suite: accessible 1 1 ___ ___ yes ___ ___ yes yes ___ with backrest as required to comply with standards
5605 Basin: handwash, accessible 1 1 ___ ___ yes ___ yes yes yes ___ short lever taps/ lever mixer
ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 1
5000 Airconditioning HVAC or ventilation
5019 Exhaust HVAC
6000 General fluorescent Lighting light switch near door; may also use motion sensor
8000 Patient/ Staff call Nurse Call 1 + indicator button & light, optional in public areas
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light, optional in public areas
8080 Emergency call Nurse Call 1 + indicator button & light, optional in public areas
9001 GPO: Double Power 1 locate near door outside room
9040 Body protected Power